2005-07-12 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHT P-1 ALL FIXTURES THAT HAVE BEEN |
| REMOVED, MOVED, OR ADDED SHALL BE SHOWN |
| ON THE RISER DIAGRAM THAT REFLECTS THE |
| CHANGE. - THE SINKIN THE HALLWAY NEXT |
| TO THE DINING ROOM IS NOT SHOWN ON THE |
| RISER DIAGRAM. THE SINK THAT WAS DELETED |
| NEAR THE MASTER BATH IS NOT SHOWN ON THE |
| SANT. RISER DIAGRAM AS BEING DELETED AND |
| CAPPED OFF. - THE LAV IN THE POWDER ROOM |
| NEXT TO THE MEDIA ROOM HAS BEEN MOVED |
| AND THE SHOWER IN THE SAME BATHROOM HAS |
| BEEN DELETED, BUT HAS NOT BEEN REFLECTED |
| ON THE SANT. RISER DIAGRAMS. SECTIONS |
| 104.2.1. & 104.3.1.1. |
| 2. ALL MEP SHEETS - ENGINEERS SHALL |
| LEGIBLY INDICATE THEIR NAME, ADDRESS, |
| AND LICENSE NUMBER ON EACH SHEET. IF |
| PRACTICING THROUGH A DULY AUTHORIZED |
| ENGINEERING BUSINESS, ENGINEERS SHALL |
| LEGIBLY INDICATE THEIRNAME AND LICENSE |
| NUMBER, AS WELL AS, THE NAME, ADDRESS, |
| AND CERTIFICATE OF AUTHROIZATION NUMBER |
| OF THE ENGINEERING BUSINESS ON EACH |
| SHEET. FAC 61G15-23.002(2) & FS 471.025. |
| |