Plan Review Notes
Plan Review Notes For Permit 05040925
Permit Number 05040925
Review Stop E
Sequence Number 2
Notes
Date Text
2006-04-24 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE SEE PLANS SHOWS TWO
 PANEL "A", THIS APPEARS TO BE A MISPRINT
 AND WOULD HAVE BEEN REDLINED, HOWEVER
 PLANS ARE COMING BACK FOR OTHER
 COMMENTS, PLEASE CORRECT AT THIS TIME.
  
 2) NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARNECES REQUIRED FOR THE DISCONNECTS
 SHOWN FOR CU'S.
 PLEASE SEE DISC'S ARE SHOWN BEHIND
 UNITS.
  
 3) NOTE: PLEASE SEE SD IN MASTER BEDRM
 IS REQUIRED TO BE LOCATED IN THE HIGHEST
 POINT OF THE TRAY/FLAT CECILING.
 NFPA-72 11.8.3.5
  
 4) NOTE: PLEASE SEE NOTES MENTIONS THE
 OLD SFBC FOR SD REQUIREMENTS. THIS
 SHOULD REFERENCE THE 2002 NFPA-72
 11.5.1.1.
  
 5) NOTE: PLEASE SEE WHAT APPEARS TO BE
 HI-HAT LOADS ON PANEL SCHEDULE(S) WHICH
 ARE SHOWN ON ONE CIRCUIT. PLEASE SEE
 PANEL "A" INDICATES HI-HATS, YET PANEL
 "B" ONLY INDICATE STHE LOAD AND ONE
 CIRCUIT.
 PLEASE SEE LOADS ONLY NEED BE ADDED TO
 SERVICE, AS CIRCUITING FOR THESE MAY BE
 IN WITH THE OTHER CIRCUITS. IF THESE ARE
 INDEED DEDICATED CIRCUITS, PLEASE LABEL
 AND KNOW, A MAX OF 1440VAIS PERMITTED
 ONA 15A CIRCUIT.
 IF THIS ONLY FOR LOADS ADDED, THIS CAN
 BE LISTED IN LOAD CALCS FOR PANELS.
 215.5
  
 6) NOTE: PLEASE SEE MISSING SW/LT FOR
 AHU ABOVE WIC AT GUEST SUITE LOCATION.
 210.70.
  
 7) NOTE: PLEASE SEE RECEPT LOCATED IN
 BATH BY VESTIBULE TO BE SHOWN AS GFI/GFI
 PROTECTED. 210.8A2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]