2005-05-31 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- SHEET T1: A) UPDATE GENERAL NOTES.
 SEE COMMENTS ON PLANS AND RETURN
 REVIEWED PAGE AFTER CORRECTIONS ARE DONE
 TO EXPEDITE THE REVIEW PROCESS.
  
 B) DESIGN PARAMETERS. CLARIFY WHERE IS
 THE BASIC VELOCITY PRESSURE TAKEN FROM.
 THIS IS NO APPLICABLE TO THE FBC. SEE
 CHAPTER 16 FBC 2001. (THIS WAS
 APPLICABLE TO THE SBC 1997)
 ALSO, CLARIFY WHY THE MIN. SOIL BEARING
 PRESSURE IS: NA?
  
 3- PROVIDE COMPLETE SPECS FOR BBQ
 SHOWING THAT IT WAS DESIGNED TO BE
 INSTALLED IN THE PORCH. SEC.2808 FBC
 2001.
  
 4- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS OR APPLY FOR A SEPARATE
 PERMIT.
  
 5- SHEET A1: A) SPECIFY COLUMNS AT BAY
 WINDOW AT MASTER BEDROOM.
  
 B) WHAT IS TS-2 SPECIFIED ON CONCRETE
 PAD BETWEEN GARAGE AND BEDROOM #2. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 C) DETAIL 5 FOR FOOTING BETWEEN GARAGE
 AND CLUB ROOM DON'T MATCH. REVISE AS
 REQUIRED.
  
 6) REVISE SIZESFOR FIXED WINDOW AT
 LIVING ROOM (36" X 234" FG ?).
  
 7) SHEET A3: A) REVISE/UPDATE TRUSS
 ANCHOR SCHEDULE. SEE LATEST CATALOGUE
 WHICH WAS REVISED TO COMPLY WITH SEC.
 1609.4.3 FBC 2001. PROVIDE COMPLETE
 ENGINEERING CALCULATIONS FOR FASTENERS
 THAT DIFFER FROM THOSE TESTED AND
 PUBLISHED BY MANUFACTURER.
  
 B) CONNECTOR THD210 IS A WOOD TO WOOD
 CONNECTOR. NEED MASONRY HANGER. SEE
 CATALOGUE FOR PROPER MASONRYCONNECTOR.
  
 C) DETAIL E/A3: CLARIFY WHY HAVING 6"
 BOLTS INTO CONCRETE. THERE IS NOT
 CONCRETE WALL TO BE ATTACHED TO? SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 8- PROVIDE FLORIDA OR APPLY FOR LOCAL
 PRODUCT APPROVAL FOR SLIDING GLASS DOORS
 WITH CORNER ASSEMBLY AS SHOWN ON PLANS.
  
 9-WINDOW AND DOOR MULLIONS: CLEARLY
 INDICATE MULLION SIZE AND FASTENERS TO
 BE USED TO VERIFY THAT IT MEETS THE
 DESIGN PRESSURES CALCULATED ON PLANS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 2001.
  
 10- DADE COUNTY NOA SUBMITTED FOR
 CASEMENT WINDOWS DOESN'T MATCH NOA
 SUBMITTTED FOR FLORIDA PRODUCT APPROVAL.
 PROVIDE MATCHING NOA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.