2005-05-31 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- SHEET T1: A) UPDATE GENERAL NOTES. |
| SEE COMMENTS ON PLANS AND RETURN |
| REVIEWED PAGE AFTER CORRECTIONS ARE DONE |
| TO EXPEDITE THE REVIEW PROCESS. |
| |
| B) DESIGN PARAMETERS. CLARIFY WHERE IS |
| THE BASIC VELOCITY PRESSURE TAKEN FROM. |
| THIS IS NO APPLICABLE TO THE FBC. SEE |
| CHAPTER 16 FBC 2001. (THIS WAS |
| APPLICABLE TO THE SBC 1997) |
| ALSO, CLARIFY WHY THE MIN. SOIL BEARING |
| PRESSURE IS: NA? |
| |
| 3- PROVIDE COMPLETE SPECS FOR BBQ |
| SHOWING THAT IT WAS DESIGNED TO BE |
| INSTALLED IN THE PORCH. SEC.2808 FBC |
| 2001. |
| |
| 4- PROVIDE COMPLETE INFORMATION FOR |
| STORM SHUTTERS OR APPLY FOR A SEPARATE |
| PERMIT. |
| |
| 5- SHEET A1: A) SPECIFY COLUMNS AT BAY |
| WINDOW AT MASTER BEDROOM. |
| |
| B) WHAT IS TS-2 SPECIFIED ON CONCRETE |
| PAD BETWEEN GARAGE AND BEDROOM #2. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| C) DETAIL 5 FOR FOOTING BETWEEN GARAGE |
| AND CLUB ROOM DON'T MATCH. REVISE AS |
| REQUIRED. |
| |
| 6) REVISE SIZESFOR FIXED WINDOW AT |
| LIVING ROOM (36" X 234" FG ?). |
| |
| 7) SHEET A3: A) REVISE/UPDATE TRUSS |
| ANCHOR SCHEDULE. SEE LATEST CATALOGUE |
| WHICH WAS REVISED TO COMPLY WITH SEC. |
| 1609.4.3 FBC 2001. PROVIDE COMPLETE |
| ENGINEERING CALCULATIONS FOR FASTENERS |
| THAT DIFFER FROM THOSE TESTED AND |
| PUBLISHED BY MANUFACTURER. |
| |
| B) CONNECTOR THD210 IS A WOOD TO WOOD |
| CONNECTOR. NEED MASONRY HANGER. SEE |
| CATALOGUE FOR PROPER MASONRYCONNECTOR. |
| |
| C) DETAIL E/A3: CLARIFY WHY HAVING 6" |
| BOLTS INTO CONCRETE. THERE IS NOT |
| CONCRETE WALL TO BE ATTACHED TO? SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 8- PROVIDE FLORIDA OR APPLY FOR LOCAL |
| PRODUCT APPROVAL FOR SLIDING GLASS DOORS |
| WITH CORNER ASSEMBLY AS SHOWN ON PLANS. |
| |
| 9-WINDOW AND DOOR MULLIONS: CLEARLY |
| INDICATE MULLION SIZE AND FASTENERS TO |
| BE USED TO VERIFY THAT IT MEETS THE |
| DESIGN PRESSURES CALCULATED ON PLANS. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC |
| 2001. |
| |
| 10- DADE COUNTY NOA SUBMITTED FOR |
| CASEMENT WINDOWS DOESN'T MATCH NOA |
| SUBMITTTED FOR FLORIDA PRODUCT APPROVAL. |
| PROVIDE MATCHING NOA. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT (561)805-6712. |