2005-06-02 00:00:00 | BUILDING REVIEW CHECKLIST: |
| |
| 1- SEE COMMENTS BY ZONING. IF HOUSE |
| NEEDS TO BE LOCATED ON THE ZERO LOT |
| LINE, THEN, OPENINGS ARE NOT ALLOWED BY |
| TABLE 600 FBC 2001. |
| |
| 2- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 3- SHEET T1: A) UPDATE GENERAL NOTES. |
| SEE COMMENTS ON PLANS. SEE RESPECTIVE |
| FBC CHAPTER FOR PROPER REFERENCE (EG: |
| CHAPTER 19 ACI 318) AND CHAPTER 35 FOR |
| PROPER REFERENCE EDITION. |
| |
| B) DESIGN PARAMETERS: CLARIFY WHERE IS |
| THE BASIC VELOCITY PRESSURE TAKEN FROM. |
| SEE SECTION 1606 FBC 2001. |
| ALSO, CLARIFY WHY THE MIN. SOIL BEARING |
| PRESSURE IS - NA?. |
| |
| 4- PROVIDE COMPLETE SPECS FOR BBQ |
| SHOWING THAT IT WAS DESIGNED TO BE |
| INSTALLED IN THE PORCH. SEC. 2808 FBC |
| 2001. |
| |
| 5- PROVIDE COMPLETE INFORMATION FOR |
| STORM SHUTTERS OR APPLY FOR A SEPARATE |
| PERMIT. |
| |
| 6- SHEET A1: A) SPECIFY COLUMNS AT BAY |
| WINDOW IN MASTER BEDROOM. |
| |
| B) WHAT DOES TS-2 SPECIFIED ON CONCRETE |
| PAD BETWEEN GARAGE AND BEDROOM #2 STANDS |
| FOR?. SEC. 104.2.1.2 CITY AMENDMENTS TO |
| FBC 2001. |
| |
| C) DETAIL 5 FOR FOOTING BETWEEN GARAGE |
| AND CLUB ROOM DOESN'T MATCH. REVISE AS |
| REQUIRED. |
| |
| 7- SHEET A2; A) NOTE #1 AND #6 CALL FOR |
| IMPACT GLAZING ON DOORS AND WINDOWS. |
| NOTE ON DESIGN PRESSURES CHART SHOWN ON |
| ELEVATIONS CALLS FOR STORM SHUTTERS. |
| CLARIFY/REVISE AS REQUIRED. |
| |
| B) REVISE SIZES FOR FIXED WINDOWS AT |
| LIVING ROOM (36' X 234" FG ?). |
| |
| C) SPECIFY SAFETY GLASS AT HIS BATH, HER |
| BATH, GUEST SUITE BATH, BATH #3 AND |
| LIVING ROOM. SEE PLANS AND SECTION |
| 2405.2 FBC 2001. |
| |
| 8- SHEET A3: A) REVISE/UPDATE TRUSS |
| ANCHOR SCHEDULE. SEE LATEST CATALOGUE |
| (2005) WHICH WAS REVISED TO COMPLY WITH |
| SEC. 1609.4.3 FBC 2001. OR, PROVIDE |
| COMPLETE ENGINEERING CALCS THAT COMPLY |
| WITH SEC. 1609.4.3 FBC 2001 FOR TYPE AND |
| NUMBER OF CONNECTORS THAT DIFFER FROM |
| THOSE TESTED AND PUBLISHED BY THE |
| MANUFACTURER. SEC. 104.2.1.2OF CITY |
| AMENDMENTS TO FBC 2001. |
| |
| B) CONNECTOR THD210 IS A WOOD TO WOOD |
| CONNECTOR. NEED MASONRY CONNECTOR. SEE |
| CATALOGUE FOR PROPER MASONRY CONNECTOR. |
| |
| C) DETAIL E/13 DOESN'T APPLY. THERE IS |
| NOT CONCRETE WALL TO BE ATTACHED TO. |
| REVISE AS REQUIRED. SEE PLANS. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| D) SPECIFY CONNECTOR FOR TRUSS GIRDER |
| RESTING ON WOOD COLUMN LOCATED IN |
| VESTIBULE FOR CLUB ROOM AND MASTER |
| BEDROOM. SEC. 104.2.1.2 CITY AMENDMENTS. |
| |
| 9- PROVIDE FLORIDA OR APPLY FOR LOCAL |
| PRODUCT APPROVAL FOR CORNER SLIDING |
| GLASS DOORS. |
| |
| 10- WINDOW AND DOOR MULLIONS: CLEARLY |
| SPECIFY MULLION SIZE AND ANCHOR TYPE TO |
| BE USED ACCORDING TO THE ASSEMBLY TO BE |
| INSTALLED ON TO VERIFY COMPLIANCE WITH |
| THE DESIGN PRESSURES. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| |
| 11- DADE COUNTY NOA SUBMITTED FOR |
| CASEMENT WINDOWS DOESN'T MATCH NOA |
| LISTED ON FLORIDA PRODUCT APPROVAL COVER |
| PAGE. REVISE AS REQUIRED. |
| |
| 12- PROVIDE COMPLETE SPECS AND LISTING |
| FOR FIREPLACE SHOWING COMPLIANCE WITH UL |
| 127 REQUIREMENTS. SEC. 2806 FBC 2001. |
| |
| ***PLEASE DON'T STAPLE PRODUCT APPROVALS |
| TO PLANS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT (561)805-6712 |
| |
| |