Plan Review Notes For Permit 05040920 |
Permit Number |
05040920 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2005-09-08 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- AS AGREED WITH G.C. A) APPLY FOR | | SHUTTERS UNDER A SEPARATE PERMIT. | | B) APPLY FOR NON-IMPACT SLIDING GLASS | | DOOR UNDER A SEPARATE PERMIT. | | 2- NEED COMPLETE SPECS FOR BBQ GRILL | | INCLUDING MODEL & HOOD FOR EXTERIOR USE. | | 3- PROVIDE PRODUCT APPROVAL FOR CASEMENT | | WINDOWS WITH LEGIBLE DRAWINGS (WITHOUT | | CUTTING INFORMATION ON TOP OR BOTTOM OF | | PAGE) AND SPECIFY GLASS TYPE TO BE USED | | TO VERIFY COMPLIANCE W/ DESIGN PRESSURES | | 4- PROVIDE COMPLETE SPECS AND UL LISTING | | FOR SEE THRU FIREPLACE AS SHOWN ON | | PLANS. AND, PROVIDE COMBUSTION AIR CALCS | | FOR MECHANICAL PLAN REVIEWER. |
|