2006-04-17 00:00:00REDLINED
  
  
 ** 110.26 FOR A/C DISC'S.
 ** AFCI FOR SD'S AS NOTE MENTIONS TO
 WIRE TO KITCHEN OR BATH LT CIRCUIT.
 210.12
 ** PANEL "A" SHOWS 50A BRKR TO PANEL
 "C", HOWEVER LOAD AND SIZE OF PANEL "C"
 IS 100A'S PER RISER AND PANEL SCHEDULE.
  
  
 THE ABOVE ARE REDLINED AND NEEDS TO BE
 CORRECTED WITH OTHER REV'S BEFORE ROUGH.