2005-07-06 00:00:00SECOND CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS OR APPLY FOR A SEPARATE
 PERMIT.
  
 3- THE BUILDING OFFICIAL IS THE ONE WHO
 APPROVES THE BBQ INSTALLATION. HE WANTS
 TO SEE TESTING AND ENGINEERING
 JUSTIFYING WHY PROPOSED INSTALLATION
 DOESN'T NEED THE EXHAUST HOOD SINCE
 THERE ARE OTHER COMPANIES WHO DESIGNED
 BBQ'S FOR LANAI OR PORCH INSTALLATION
 AND THEY REQUIRE HOOD EXHAUST.
 LETTER SUBMITTED IS INSUFFICIENT AND IS
 SIGNED BY NOBODY. BESIDES, MANUFACTURER
 SPECS SAYS FOR OUTDOOR INSTALLATION ONLY
  
 4- SHEET A3: A) REVISE/UPDATE TRUSS
 ANCHOR SCHEDULE (NOT DONE FROM PREVIOUS
 CHECKLIST). SEE LATEST CATALOGUE WHICH
 WAS REVISED TO COMPLY WITH SECTION
 1609.4.3 FBC 2001. PROVIDE TESTING AND
 ENGINEERING CALCS FOR NUMBER AND SIZE OF
 NAILS THAT DIFFER FROM THOSE ALREADY
 TESTED AND PUBLISHED BY MANUFACTURER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 B) CONNECTOR THD210 IS A WOOD TO WOOD
 CONNECTOR. NEED TO SPECIFY MASONRY
 CONNECTOR. SEE CATALOGUE FOR PROPER
 MASONRY CONNECTOR.
  
 C) SPECIFY CONNECTOR FOR TRUSS GIRDER
 END AT INTERSECTION OF MASTER BEDROOM
 AND CLUB ROOM CORNER. SEE PLANS.
  
 5- A)SLIDING GLASS DOORS NOA AND FLORIDA
 PRODUCT APPROVAL DON'T CORRESPOND TO
 EACH OTHER.
 B) NOA SUBMITTED IS FOR IMPACT DOORS.
 ARE IMPACT DOORS GOING TO BE INSTALLED?
  
 6- MULLIONS SPECIFIED FOR WINDOWS AT
 LIVING ROOM DON'T RESIST CALCULATED
 DESIGN PRESSURES. REVISE SIZE OF
 MULLIONS AND PROVIDE PRODUCT APPROVAL
 AS REQUIRED.
  
 7- DADE COUNTY NOA SUBMITTED FOR
 CASEMENT WINDOWS DOESN'T MATCH NOA
 LISTED IN THE FLORIDA PRODUCT APPROVAL.
 REVISE AS REQUIRED AND MAKE SURE IS THE
 TYPE OF WINDOW ASSEMBLY TO BE INSTALLED.
  
 8- REAR ELEVATION DOESN'T MATCH FLOOR
 PLAN. REVISE LIVING ROOM WINDOW AND
 CABANA BATH WING TO MATCH FLOOR PLAN.
  
 9- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR IMPACT GLASS CASEMENT
 WINDOW FOR BREAKFAST AREA.
  
 10- PROVIDE ENERGY CALCULATIONS SHOWING
 WORST CASE SCENARIO FOR THIS MODEL.
 CALCULATIONS TO MATCH FLOOR PLAN. SEE
 OVERHANG LENGTH AND HEIGHT, SIZES OF
 WINDOWS/DOORS ETC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.