2005-07-06 00:00:00 | SECOND CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- PROVIDE COMPLETE INFORMATION FOR |
| STORM SHUTTERS OR APPLY FOR A SEPARATE |
| PERMIT. |
| |
| 3- THE BUILDING OFFICIAL IS THE ONE WHO |
| APPROVES THE BBQ INSTALLATION. HE WANTS |
| TO SEE TESTING AND ENGINEERING |
| JUSTIFYING WHY PROPOSED INSTALLATION |
| DOESN'T NEED THE EXHAUST HOOD SINCE |
| THERE ARE OTHER COMPANIES WHO DESIGNED |
| BBQ'S FOR LANAI OR PORCH INSTALLATION |
| AND THEY REQUIRE HOOD EXHAUST. |
| LETTER SUBMITTED IS INSUFFICIENT AND IS |
| SIGNED BY NOBODY. BESIDES, MANUFACTURER |
| SPECS SAYS FOR OUTDOOR INSTALLATION ONLY |
| |
| 4- SHEET A3: A) REVISE/UPDATE TRUSS |
| ANCHOR SCHEDULE (NOT DONE FROM PREVIOUS |
| CHECKLIST). SEE LATEST CATALOGUE WHICH |
| WAS REVISED TO COMPLY WITH SECTION |
| 1609.4.3 FBC 2001. PROVIDE TESTING AND |
| ENGINEERING CALCS FOR NUMBER AND SIZE OF |
| NAILS THAT DIFFER FROM THOSE ALREADY |
| TESTED AND PUBLISHED BY MANUFACTURER. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| B) CONNECTOR THD210 IS A WOOD TO WOOD |
| CONNECTOR. NEED TO SPECIFY MASONRY |
| CONNECTOR. SEE CATALOGUE FOR PROPER |
| MASONRY CONNECTOR. |
| |
| C) SPECIFY CONNECTOR FOR TRUSS GIRDER |
| END AT INTERSECTION OF MASTER BEDROOM |
| AND CLUB ROOM CORNER. SEE PLANS. |
| |
| 5- A)SLIDING GLASS DOORS NOA AND FLORIDA |
| PRODUCT APPROVAL DON'T CORRESPOND TO |
| EACH OTHER. |
| B) NOA SUBMITTED IS FOR IMPACT DOORS. |
| ARE IMPACT DOORS GOING TO BE INSTALLED? |
| |
| 6- MULLIONS SPECIFIED FOR WINDOWS AT |
| LIVING ROOM DON'T RESIST CALCULATED |
| DESIGN PRESSURES. REVISE SIZE OF |
| MULLIONS AND PROVIDE PRODUCT APPROVAL |
| AS REQUIRED. |
| |
| 7- DADE COUNTY NOA SUBMITTED FOR |
| CASEMENT WINDOWS DOESN'T MATCH NOA |
| LISTED IN THE FLORIDA PRODUCT APPROVAL. |
| REVISE AS REQUIRED AND MAKE SURE IS THE |
| TYPE OF WINDOW ASSEMBLY TO BE INSTALLED. |
| |
| 8- REAR ELEVATION DOESN'T MATCH FLOOR |
| PLAN. REVISE LIVING ROOM WINDOW AND |
| CABANA BATH WING TO MATCH FLOOR PLAN. |
| |
| 9- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR IMPACT GLASS CASEMENT |
| WINDOW FOR BREAKFAST AREA. |
| |
| 10- PROVIDE ENERGY CALCULATIONS SHOWING |
| WORST CASE SCENARIO FOR THIS MODEL. |
| CALCULATIONS TO MATCH FLOOR PLAN. SEE |
| OVERHANG LENGTH AND HEIGHT, SIZES OF |
| WINDOWS/DOORS ETC. |
| |
| |