2005-06-01 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- SHEET T1: A) UPDATE GENERAL NOTES. |
| SEE COMMENTS ON PLANS AND RETURN |
| REVIEWED SET AFTER CORRECTIONS ARE DONE |
| TO ORIGINAL DRAWINGS TO EXPEDITE REVIEW. |
| |
| 3- DESIGN PARAMETERS: CLARIFY WHERE IS |
| THE BASIC VELOCITY PRESSURE TAKEN FROM. |
| SEE SEC. 1606 FBC 2001. |
| ALSO, CLARIFY WHY THE MIN. SOIL BEARING |
| PRESSURE IS -NA? |
| |
| 4- PROVIDE COMPLETE INFORMATION FOR |
| STORM SHUTTERS OR APPLY FOR A SEPARATE |
| PERMIT. |
| |
| 5- SHEET A1: A) COLUMNS AT LANAI WERE |
| KEYED WRONG. THEY SHOULD BE C4 NOT C2. |
| SEE COMMENTS ON PLANS & REVISE AS REQ'D. |
| |
| B) DETAIL 4 DOESN'T MATCH FOOTING SHOWN |
| ON PLAN BETWEEN BEDROOM #2 AND GARAGE. |
| REVISE AS REQUIRED. |
| |
| 6- SHEET A2: A) SPECIFY SAFETY GLASS FOR |
| WINDOWS AT HER BATH, HIS BATH AND LIVING |
| ROOM. SEC. 2405.2 FBC 2001. |
| |
| B) CLARIFY NOTE #6. ARE WINDOWS AND |
| DOORS HAVING IMPACT GLAZING OR STORM |
| SHUTTERS?. SEE NOTE UNDER DESIGN |
| PRESSURES CHART AND REVISE AS REQ'D. |
| |
| 7- PROVIDE COMPLETE BBQ SPECS STATING |
| THAT GRILL IS DESIGNED TO BE INSTALLED |
| IN PORCH OR LANAI. SEC. 2808 FBC 2001. |
| |
| 8- SHEET A3: A) REVISE/UPDATE TRUSS |
| ANCHOR SCHEDULE. SEE LATEST CATALOGUE |
| WHICH WAS REVISED TO COMPLY WITH SEC. |
| 1609.4.3 FBC 2001. PROVIDE COMPLETE |
| ENGINEERING CALCULATIONS SHOWING |
| COMPLIANCE WITH SEC. 1609.4.3 FBC 2001 |
| FOR FASTENERS TYPE AND SPACING THAT |
| DIFFER FROM THOSE TESTED AND PUBLISHED |
| BY THE MANUFACTURER. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| B) CONNECTOR THD210 IS A WOOD TO WOOD |
| CONNECTOR. NEED TO SPECIFY WOOD TO |
| MASONRY HANGER. SEE CATALOGUE FOR PROPER |
| MASONRY CONNECTORS AND REVISE AS |
| REQUIRED. |
| |
| C) SPECIFY CONNECTOR FOR TRUSS GIRDER |
| END AT INTERSECTION OF MASTER BEDROOM |
| AND CLUB ROOM CORNER. SEE PLANS. |
| |
| 9- APPLY FOR LOCAL PRODUCT APPROVAL FOR |
| CORNER SLIDING GLASS DOORS. DADE COUNTY |
| NOA ALONE IS NOT AUTOMATICALLY A FLORIDA |
| PRODUCT APPROVAL. FILL OUT APPLICATION |
| FOR LOCAL PRODUCT APPROVAL. SEE |
| WWW.FLORIDABUILDING.ORG. |
| |
| 10- WINDOW AND DOOR MULLIONS: CLEARLY |
| INDICATE SIZE AND ANCHOR TYPE ACCORDING |
| TO ASSEMBLY TO VERIFY COMPLIANCE WITH |
| DESIGN PRESSURES. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 11- DADE COUNTY NOA SUBMITTED FOR |
| CASEMENT WINDOWS DOESN'T MATCH NOA |
| LISTED ON FLORIDA PRODUCT APPROVAL COVER |
| PAGE. REVISE AS REQUIRED. |
| |
| 12- PROVIDE COMPLETE LISTING FOR |
| FIREPLACE SHOWING COMPLIANCE WITH UL 127 |
| REQUIREMENTS. SEC. 2806 FBC 2001. |
| |
| *** PLEASE DON'T STAPLE PRODUCT |
| APPROVALS TO PLANS. IT WILL EXPEDITE |
| REVIEW PROCESS AND HANDLING OF PLANS. |
| |