Plan Review Notes
Plan Review Notes For Permit 05040918
Permit Number 05040918
Review Stop E
Sequence Number 4
Notes
Date Text
2006-03-13 00:00:00REDLINED:
 VIF THE OCP FOR AHU #2 IS TOO SMALL,
 THIS SHALL BE SIZED AT A MIN OF 125%.
  
 NFPA-72 HAS CHANGE TO 2002 11.5.1.1, AND
 11.8.3.5