Plan Review Notes For Permit 05040918 |
Permit Number |
05040918 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-12-09 00:00:00 | BUILDING REVIEW PROVISO: | | 1- APPLY FOR STORM SHUTTERS AS AGREED ON | | PROVISO. NOTE: APPLY AS SOON AS POSSIBLE | | TO AVOID DELAYS OR CONFLICTS GIVEN THE | | HIGH VOLUME OF PERMIT APPLICATIONS THE | | CITY IS RECEIVING. | | | | 2- SINGLE HUNG WINDOWS CUT SHEETS: | | A) THE PURPOSE OF CUT SHEETS IS TO | | VERIFY COMPLIANCE WITH EGRESS | | REQUIREMENTS: 24" MIN. CLEAR HEIGHT AND | | 5.7 S.F. MIN. TOTAL CLEAR OPENING. | | INFORMATION SUBMITTED DOESN'T PROVIDE | | THIS INFORMATION. | | B) CUT SHEETS ARE COMING FROM S&P | | ARCHITECTURAL PRODUCTS. PRODUCT APPROVAL | | SUBMITTED IS FOR PGT WINDOWS. | | CLARIFY/REVISE AS REQUIRED. | | C) ARCHITECT OF RECORD TO REVIEW CUT | | SHEETS TO VERIFY DESIGN CRITERIA AND | | EGRESS COMPLIANCE WITH SEC. 1005.4.4 FBC | | 2001 PRIOR TO SUBMITTAL TO THIS OFFICE. | | D) SEE 2ND FLOOR PLANS FOR SIZE OF | | WINDOWS SPECIFIED. NEED CUT SHEETS FOR | | ALL SPECIFIED SIZES. | | | | 3- STAIR SHOP DRAWINGS NEED TO BE SIGNED | | AND SEALED BY THE ENGINEER, ORLANDO M. | | FORTUN AS REQUIRED BY CHAPTER 471 | | FLORIDA STATUTES. | | | | 4- OWES $70.00 FOR REVISION FEES. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|