2005-04-25 00:00:00 | ********UNSAT ********* |
| |
| 1)NOTE: PLEASE SEE PANEL "B" (2P80A) |
| FEEDING #12 AWG.PLEASE SEE 310.16,240.4 |
| |
| 2)NOTE: PLEASE SEE SOME MISSING RECEPTS |
| PER 210.52 |
| |
| 3)NOTE: PLEASE SEE CODES REFERENCED IN |
| NOTES ARE FROM THE 1996 NEC. PLEASE SEE |
| NEW REVISED ARTS. IN 2002 NEC. |
| |
| 4)NOTE: PLEASE SEE SD'S SHOWN ON MORE |
| THAN ONE CIRCUIT. |
| PLEASE SEE ALL SD'S ARE REQUIRED TO BE |
| WIRED "INLINE". THEY CAN NOT BE WIRED |
| INLINE AND BE ON TWO SEPARATE |
| PHASES/CIRCUITS. |
| NEC |
| |
| 5)NOTE: PLEASE CORRELATE CIRCUITING ON |
| PLANS WITH PANEL SCHEDULE. |
| PLEASE SEE A-21 FOR OVEN ALSO SHOWN FOR |
| SD'S. |
| PLEASE SEE OVEN SHOWN ON PLANS AS SPACE? |
| ETC. |
| |
| 6)NOTE: PLEASE LABEL PANEL IN GARAGE. |
| PLEASE VERIFY PANEL "B WHICH IS SHOWN |
| NEXT TO METER, BUT BEING FED FROM PANEL |
| "A" LOCATED INSIDE. |
| PLEASE ALSO SEE MIN CLEARENCE FOR PANEL |
| "B". 110.26 |
| |
| 7)NOTE: PLEASE VERIFY KW LOAD FOR OVEN. |
| (THIS IS ONLY A NOTE). |
| |
| PLEASE SEE SOME OF THE ABOVE ITEMS HAVE |
| BEEN REDLINED IN SOME LOCATIONS ON PLANS |
| FOR ABOVE COMMENTS. |
| |
| PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |