Plan Review Notes
Plan Review Notes For Permit 05040918
Permit Number 05040918
Review Stop E
Sequence Number 1
Notes
Date Text
2005-04-25 00:00:00********UNSAT *********
  
 1)NOTE: PLEASE SEE PANEL "B" (2P80A)
 FEEDING #12 AWG.PLEASE SEE 310.16,240.4
  
 2)NOTE: PLEASE SEE SOME MISSING RECEPTS
 PER 210.52
  
 3)NOTE: PLEASE SEE CODES REFERENCED IN
 NOTES ARE FROM THE 1996 NEC. PLEASE SEE
 NEW REVISED ARTS. IN 2002 NEC.
  
 4)NOTE: PLEASE SEE SD'S SHOWN ON MORE
 THAN ONE CIRCUIT.
 PLEASE SEE ALL SD'S ARE REQUIRED TO BE
 WIRED "INLINE". THEY CAN NOT BE WIRED
 INLINE AND BE ON TWO SEPARATE
 PHASES/CIRCUITS.
 NEC
  
 5)NOTE: PLEASE CORRELATE CIRCUITING ON
 PLANS WITH PANEL SCHEDULE.
 PLEASE SEE A-21 FOR OVEN ALSO SHOWN FOR
 SD'S.
 PLEASE SEE OVEN SHOWN ON PLANS AS SPACE?
 ETC.
  
 6)NOTE: PLEASE LABEL PANEL IN GARAGE.
 PLEASE VERIFY PANEL "B WHICH IS SHOWN
 NEXT TO METER, BUT BEING FED FROM PANEL
 "A" LOCATED INSIDE.
 PLEASE ALSO SEE MIN CLEARENCE FOR PANEL
 "B". 110.26
  
 7)NOTE: PLEASE VERIFY KW LOAD FOR OVEN.
 (THIS IS ONLY A NOTE).
  
 PLEASE SEE SOME OF THE ABOVE ITEMS HAVE
 BEEN REDLINED IN SOME LOCATIONS ON PLANS
 FOR ABOVE COMMENTS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW