2005-05-31 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- FLOOR PLANS SHOW HANDRAIL ON ONE SIDE |
| OF STAIRS ONLY. NEED HANDRAIL AT RUN |
| THAT GOES FROM LANDING TO 2ND FLOOR. |
| SEC. 1007.5.1 EXCEPTION #3. |
| |
| 3- DESIGNER OF RECORD TO SPECIFY ROOF |
| TILE FASTENING AS REQ'D BY SEC. |
| 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| |
| 4- SPECIFY CONTROL JOINTS OR SPECIFY WWM |
| SUPPORTS AND SPACING AS REQ'D BY SEC. |
| 1909.3 FBC 2001. |
| |
| 5- SPECIFY ROOF SHEATHING NAIL SIZE AND |
| SPACING. SEE TABLE 2306.1 OF CITY |
| AMENDMENTS TO FBC 2001 FOR MEAN ROOF |
| HEIGHT ABOVE 25'-0" FOR ZONES 1,2 AND 3. |
| |
| 6- PROVIDE ATTIC ACCESS AT MASTER |
| BEDROOM WING. SEC. 2309.6 FBC 2001. |
| |
| 7- PROVIDE CUT SHEETS FOR 24SH WINDOWS |
| SHOWING COMPLIANCE WITH MIN. EGRESS |
| OPENING OF 5.7SF. AS REQUIRED BY SEC. |
| 1005.4.4 FBC 2001. |
| NOTE: PRODUCT APPROVAL SUBMITTED DOESN'T |
| HAVE THIS SIZE WINDOWS. |
| |
| 8- REVISE NOTE #3 ON SHEET A-3.1. NEED |
| 7/8" STUCCO THICKNESS. NO 5/8". SEE ASTM |
| C-926. |
| |
| 9- PROVIDE DETAIL/SPECS FOR CEILING |
| INSTALLATION AT ENTRY AND REAR PORCH. |
| SEE ASTM C-926 AND C-1063. SPECIFY |
| FASTENER SIZE AND SPACING. |
| |
| 10- SHEET A-7: A) REVISE STAIR KEY NOTE |
| #1. HANDRAIL TO BE BETWEEN 34" AND 38" |
| AS REQ'D BY SEC. 1007.5.1 EXCEPTION #3. |
| NOTE: HANDRAIL AND GUARDRAIL ARE NOT THE |
| SAME THING. |
| |
| B) SPECIFY MATERIAL AND LOCATION OF |
| FIREBLOCKING AT STAIRS. ALSO MISSING |
| FIREBLOCKING AT TOP OF STAIRS. SEC. |
| 2305.1.4 FBC 2001. |
| |
| C) SPECIFY ALL FASTENERS FOR STAIR |
| FRAMING. SEC. 104.2.1.2 CITY AMENDMENTS |
| TO FBC 2001. |
| |
| 11- PROVIDE CALCULATIONS SHOWING HOW 2 |
| STORY STRUCTURE ONLY REQUIRES 2000PSF |
| SOIL BEARING CAPACITY. SEC. 104.2.1.2 |
| CITY AMMENDMENTS TO FBC 2001. |
| |
| 12- THERE ARE 2 GARAGE DOOR BUCK DETAILS |
| WITH DIFFERENT SPECS.CLARIFY WHICH ONE |
| APPLIES TO THIS JOB. SEE SHEET A-6 AND |
| SHEET S-4. |
| |
| 13- SPECIFY DRAFSTOPPING LOCATION AND |
| MATERIAL ON 2ND FLOOR FRAMING PLAN AS |
| REQ'D BY SEC. 2305.2.2.1 FBC 2001. |
| |
| 14- PROVIDE SMOKE DETECTOR AT FIRST |
| FLOOR IN CLOSE PROXIMITY TO STAIRS. |
| ELECTRICAL PLAN SHOWS SMOKE DETECTOR ON |
| FOYER CEILING WHICH IS A DOUBLE VOLUME |
| CEILING. SEC. 905.2.2 FBC 2001. |
| |
| 15- SHEET S-1: A) UPDATE STRUCTURAL |
| NOTES 2(B) AND 3(A). SEE CHAPTER 19 FOR |
| PROPER ACI REFERENCE AND CHAPTER 35 FOR |
| PROPER EDITION. |
| |
| B) DETAIL #6 FOR PRIVACY WALL IS FOR |
| 6'-0" HIGH WALL. FIRST FLOOR PLAN CALLS |
| FOR 8'-0" HIGH WALL. REVISE AS REQ'D. |
| |
| C) FOOTING FOR COLUMN AT REAR PORCH IS |
| ENCROACHING INTO NEIGHBOR'S PROPERTY AT |
| ZERO LOT LINE. REVISE AS REQUIRED. |
| |
| D) STEEL COLUMN BY AHU #1 CALLS FOR F30 |
| FOOTING. THERE IS NOT F30 ON FOOTING |
| SCHEDULE. REVISE AS REQUIRED. |
| |
| E) SPECIFY CONNECTORS AT TOP OF ALL WOOD |
| COLUMNS. SEC. 104.2.1.2 CITY AMENDMENTS |
| TO FBC 2001. |
| |
| F) SOIL STATEMENT. DESIGNER OF RECORD TO |
| REVIEW SOIL TEST REPORT. THERE IS NO |
| LIMEROCK. |
| ALSO, REPORT RECOMMENDS 18" MIN. WIDTH |
| FOR FOOTINGS. FOOTING M-16 CALLS FOR 16" |
| WIDTH. SPECIFY IF DESIGNER REVIEWED SOIL |
| TEST REPORT AND FOOTING RECOMMENDATION |
| IS NOT REQUIRED. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 16- SHEET S-2: A) FRAMING PLAN CALLS FOR |
| CONNECTOR #22. WHERE IS IT ON THE TRUSS |
| CONNECTOR SCHEDULE? |
| |
| B) CONNECTOR #5 IS A WOOD TO WOOD |
| CONNECTOR. NEED WOOD TO MASONRY |
| CONNECTOR. REVISE AS REQUIRED. |
| |
| C) THERE IS OVERLAPPING INFORMATION BY |
| MASTER BEDROOM ROOF AREA. REVISE. |
| |
| D) COLUMN BY STAIRWAY SAYS STEEL COLUMN |
| DETAIL #38. FOUNDATION PLAN CALLS FOR |
| WOOD COLUMN. REVISE AS REQUIRED. |
| |
| E) SPECIFY CONNECTOR FOR TRUSS GIRDER |
| ABOVE LAUNDRY AREA. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 17- SHEET S-3: A) CONNECTOR SCHEDULE: |
| REVISE NUMBER AND TYPE OF NAILS. SEE |
| LATEST CATALOGUE FOR PROPER NUMBER OF |
| NAILS. |
| |
| B) WHERE IS CONNECTOR #22? |
| |
| C) REVISE CONNECTOR #5. NEED WOOD TO |
| MASONRY CONNECTOR. |
| |
| 18- SHEET S-5: A) DETAIL 38. THERE ARE |
| NOT SPECS FOR SIZE AND NUMBER OF BOLTS. |
| |
| B) DETAIL 50: NEED TO SPECIFY WOOD TO |
| MASONRY STRAPS. SEE CATALOGUE FOR |
| MASONRY CONNECTORS. |
| |
| 19- ENTRY DOOR PRODUCT APPROVAL |
| SUBMITTED IS FOR 6'-8" DOORS. NEED 8'-0" |
| HIGH DOORS. |
| |
| 20- REVISE ENERGY CALCULATIONS. THERE IS |
| NOT EXTERIOR FRAMED WALLS. 2ND FLOOR IS |
| MASONRY TOO. |
| |
| 21- SURVEYOR NEED TO SIGN AND DATE |
| SURVEY AS REQUIRED BY CHAPTER 471 |
| FLORIDA STATUTES. |
| |
| 22- PROVIDE COMPLETE INFORMATION FOR |
| STORM SHUTTERS OR APPLY FOR A SEPARATE |
| PERMIT. |
| |