Plan Review Notes
Plan Review Notes For Permit 05040918
Permit Number 05040918
Review Stop B
Sequence Number 1
Notes
Date Text
2005-05-31 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- FLOOR PLANS SHOW HANDRAIL ON ONE SIDE
 OF STAIRS ONLY. NEED HANDRAIL AT RUN
 THAT GOES FROM LANDING TO 2ND FLOOR.
 SEC. 1007.5.1 EXCEPTION #3.
  
 3- DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQ'D BY SEC.
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 4- SPECIFY CONTROL JOINTS OR SPECIFY WWM
 SUPPORTS AND SPACING AS REQ'D BY SEC.
 1909.3 FBC 2001.
  
 5- SPECIFY ROOF SHEATHING NAIL SIZE AND
 SPACING. SEE TABLE 2306.1 OF CITY
 AMENDMENTS TO FBC 2001 FOR MEAN ROOF
 HEIGHT ABOVE 25'-0" FOR ZONES 1,2 AND 3.
  
 6- PROVIDE ATTIC ACCESS AT MASTER
 BEDROOM WING. SEC. 2309.6 FBC 2001.
  
 7- PROVIDE CUT SHEETS FOR 24SH WINDOWS
 SHOWING COMPLIANCE WITH MIN. EGRESS
 OPENING OF 5.7SF. AS REQUIRED BY SEC.
 1005.4.4 FBC 2001.
 NOTE: PRODUCT APPROVAL SUBMITTED DOESN'T
 HAVE THIS SIZE WINDOWS.
  
 8- REVISE NOTE #3 ON SHEET A-3.1. NEED
 7/8" STUCCO THICKNESS. NO 5/8". SEE ASTM
 C-926.
  
 9- PROVIDE DETAIL/SPECS FOR CEILING
 INSTALLATION AT ENTRY AND REAR PORCH.
 SEE ASTM C-926 AND C-1063. SPECIFY
 FASTENER SIZE AND SPACING.
  
 10- SHEET A-7: A) REVISE STAIR KEY NOTE
 #1. HANDRAIL TO BE BETWEEN 34" AND 38"
 AS REQ'D BY SEC. 1007.5.1 EXCEPTION #3.
 NOTE: HANDRAIL AND GUARDRAIL ARE NOT THE
 SAME THING.
  
 B) SPECIFY MATERIAL AND LOCATION OF
 FIREBLOCKING AT STAIRS. ALSO MISSING
 FIREBLOCKING AT TOP OF STAIRS. SEC.
 2305.1.4 FBC 2001.
  
 C) SPECIFY ALL FASTENERS FOR STAIR
 FRAMING. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 11- PROVIDE CALCULATIONS SHOWING HOW 2
 STORY STRUCTURE ONLY REQUIRES 2000PSF
 SOIL BEARING CAPACITY. SEC. 104.2.1.2
 CITY AMMENDMENTS TO FBC 2001.
  
 12- THERE ARE 2 GARAGE DOOR BUCK DETAILS
 WITH DIFFERENT SPECS.CLARIFY WHICH ONE
 APPLIES TO THIS JOB. SEE SHEET A-6 AND
 SHEET S-4.
  
 13- SPECIFY DRAFSTOPPING LOCATION AND
 MATERIAL ON 2ND FLOOR FRAMING PLAN AS
 REQ'D BY SEC. 2305.2.2.1 FBC 2001.
  
 14- PROVIDE SMOKE DETECTOR AT FIRST
 FLOOR IN CLOSE PROXIMITY TO STAIRS.
 ELECTRICAL PLAN SHOWS SMOKE DETECTOR ON
 FOYER CEILING WHICH IS A DOUBLE VOLUME
 CEILING. SEC. 905.2.2 FBC 2001.
  
 15- SHEET S-1: A) UPDATE STRUCTURAL
 NOTES 2(B) AND 3(A). SEE CHAPTER 19 FOR
 PROPER ACI REFERENCE AND CHAPTER 35 FOR
 PROPER EDITION.
  
 B) DETAIL #6 FOR PRIVACY WALL IS FOR
 6'-0" HIGH WALL. FIRST FLOOR PLAN CALLS
 FOR 8'-0" HIGH WALL. REVISE AS REQ'D.
  
 C) FOOTING FOR COLUMN AT REAR PORCH IS
 ENCROACHING INTO NEIGHBOR'S PROPERTY AT
 ZERO LOT LINE. REVISE AS REQUIRED.
  
 D) STEEL COLUMN BY AHU #1 CALLS FOR F30
 FOOTING. THERE IS NOT F30 ON FOOTING
 SCHEDULE. REVISE AS REQUIRED.
  
 E) SPECIFY CONNECTORS AT TOP OF ALL WOOD
 COLUMNS. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 F) SOIL STATEMENT. DESIGNER OF RECORD TO
 REVIEW SOIL TEST REPORT. THERE IS NO
 LIMEROCK.
 ALSO, REPORT RECOMMENDS 18" MIN. WIDTH
 FOR FOOTINGS. FOOTING M-16 CALLS FOR 16"
 WIDTH. SPECIFY IF DESIGNER REVIEWED SOIL
 TEST REPORT AND FOOTING RECOMMENDATION
 IS NOT REQUIRED. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 16- SHEET S-2: A) FRAMING PLAN CALLS FOR
 CONNECTOR #22. WHERE IS IT ON THE TRUSS
 CONNECTOR SCHEDULE?
  
 B) CONNECTOR #5 IS A WOOD TO WOOD
 CONNECTOR. NEED WOOD TO MASONRY
 CONNECTOR. REVISE AS REQUIRED.
  
 C) THERE IS OVERLAPPING INFORMATION BY
 MASTER BEDROOM ROOF AREA. REVISE.
  
 D) COLUMN BY STAIRWAY SAYS STEEL COLUMN
 DETAIL #38. FOUNDATION PLAN CALLS FOR
 WOOD COLUMN. REVISE AS REQUIRED.
  
 E) SPECIFY CONNECTOR FOR TRUSS GIRDER
 ABOVE LAUNDRY AREA. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 17- SHEET S-3: A) CONNECTOR SCHEDULE:
 REVISE NUMBER AND TYPE OF NAILS. SEE
 LATEST CATALOGUE FOR PROPER NUMBER OF
 NAILS.
  
 B) WHERE IS CONNECTOR #22?
  
 C) REVISE CONNECTOR #5. NEED WOOD TO
 MASONRY CONNECTOR.
  
 18- SHEET S-5: A) DETAIL 38. THERE ARE
 NOT SPECS FOR SIZE AND NUMBER OF BOLTS.
  
 B) DETAIL 50: NEED TO SPECIFY WOOD TO
 MASONRY STRAPS. SEE CATALOGUE FOR
 MASONRY CONNECTORS.
  
 19- ENTRY DOOR PRODUCT APPROVAL
 SUBMITTED IS FOR 6'-8" DOORS. NEED 8'-0"
 HIGH DOORS.
  
 20- REVISE ENERGY CALCULATIONS. THERE IS
 NOT EXTERIOR FRAMED WALLS. 2ND FLOOR IS
 MASONRY TOO.
  
 21- SURVEYOR NEED TO SIGN AND DATE
 SURVEY AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES.
  
 22- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS OR APPLY FOR A SEPARATE
 PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.