Plan Review Notes
Plan Review Notes For Permit 05040914
Permit Number 05040914
Review Stop B
Sequence Number 3
Notes
Date Text
2005-08-31 00:00:00SUBMITTAL BUILDING REVIEW CHECKLIST:
 1- SEPARATE PERMIT FOR SHUTTERS HAS NOT
 BEEN APPLIED FOR YET.
  
 2- ROOF FRAMING PLAN: CONNECTORS NEED TO
 BE REVISED AT ENTRY FOYER AREA. TRUSSES
 ARE RESTING ON A GIRDER TRUSS, NOT ON A
 CONCRETE BEAM. REVISE AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 3- TRUSS ANCHOR SCHEDULE: REVISE NUMBER
 OF NAILS SPECIFIED FOR CONNECTOR HUS26.
 SEE 2005 CATALOGUE.
  
 4- ONE HOUR FIRE RATED DOOR AT ATRIUM
 PRODUCT APPROVAL SUBMITTED IS FOR
 OUTSWING DOOR. PLANS SHOW INSWING DOOR.
 REVISE AS REQUIRED.
 ***NOTE: DOOR AT THIS LOCATION NEED NOT
 TO BE FIRE RATED. WALL IS NOT LOCATED IN
 THE ZERO LOT LINE. BESIDES, THIS WALL IS
 MORE LIKE A FENCE NOT A BUILDING WALL.
 THEREFORE, TABLE 600 FBC 2001 DOESN'T
 APPLY.
  
 5- WINDOW MULLION SIZE SPECIFIED FOR
 FIXED WINDOWS AT GREAT ROOM DOESN'T
 RESIST THE CALCULATED DESIGN PRESSURES.
 SEE PRODUCT APPROVAL AND REVISE SIZE AS
 REQUIRED. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 6- ALL REVISED DRAWINGS WILL BE SUBJECT
 TO THE REVISION FEES. SEE THE SUBMITTAL
 FORM FOR APPLICABLE FEES.
  
 7- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR FRENCH DOORS. SEE PLANS FOR
 REQUIRED SIZE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.