2005-08-31 00:00:00 | SUBMITTAL BUILDING REVIEW CHECKLIST: |
| 1- SEPARATE PERMIT FOR SHUTTERS HAS NOT |
| BEEN APPLIED FOR YET. |
| |
| 2- ROOF FRAMING PLAN: CONNECTORS NEED TO |
| BE REVISED AT ENTRY FOYER AREA. TRUSSES |
| ARE RESTING ON A GIRDER TRUSS, NOT ON A |
| CONCRETE BEAM. REVISE AS REQUIRED. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 3- TRUSS ANCHOR SCHEDULE: REVISE NUMBER |
| OF NAILS SPECIFIED FOR CONNECTOR HUS26. |
| SEE 2005 CATALOGUE. |
| |
| 4- ONE HOUR FIRE RATED DOOR AT ATRIUM |
| PRODUCT APPROVAL SUBMITTED IS FOR |
| OUTSWING DOOR. PLANS SHOW INSWING DOOR. |
| REVISE AS REQUIRED. |
| ***NOTE: DOOR AT THIS LOCATION NEED NOT |
| TO BE FIRE RATED. WALL IS NOT LOCATED IN |
| THE ZERO LOT LINE. BESIDES, THIS WALL IS |
| MORE LIKE A FENCE NOT A BUILDING WALL. |
| THEREFORE, TABLE 600 FBC 2001 DOESN'T |
| APPLY. |
| |
| 5- WINDOW MULLION SIZE SPECIFIED FOR |
| FIXED WINDOWS AT GREAT ROOM DOESN'T |
| RESIST THE CALCULATED DESIGN PRESSURES. |
| SEE PRODUCT APPROVAL AND REVISE SIZE AS |
| REQUIRED. SEC. 104.2.1.2 CITY AMENDMENTS |
| TO FBC 2001. |
| |
| 6- ALL REVISED DRAWINGS WILL BE SUBJECT |
| TO THE REVISION FEES. SEE THE SUBMITTAL |
| FORM FOR APPLICABLE FEES. |
| |
| 7- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR FRENCH DOORS. SEE PLANS FOR |
| REQUIRED SIZE. |
| |