Plan Review Notes For Permit 05040914 |
Permit Number |
05040914 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-06-28 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- CONTRACTOR AGREED TO APPLY FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 2- SUBMIT SOIL TEST REPORT WITH FOOTING | | SIZE REVISION. | | 3- ROOF FRAMING PLAN: REVISE CONNECTOR | | SPECIFIED AT FRONT PORCH MASONRY BEAM. | | NEED MASONRY CONNECTOR. SEE DETAIL 5/D1. | | **NOTE: ROOF FRAMING PLAN CALLS FOR | | DETAIL 6/D1. REVISE FOR 5/D1. | | 4- TRUSS ANCHOR SCHEDULE: REVISE SIZE OF | | NAIL USED FOR HUS26. SEE CATALOGUE. | | 5- PROVIDE PRODUCT APPROVAL FOR: | | A) 1 HR FIRE RATED ASSEMBLY EGRESS OP'G. | | | | B) FRENCH DOORS AS SHOWN ON PLANS. | | C) 8'-0" HIGH ENTRY DOORS. | | 6- PROVIDE CLEAR WINDOW AND DOOR | | SCHEDULES WITH MATCHING SYMBOLS. | | 7- PROVIDERECORDED EGRESS EASEMENT. | | 8- REVISE SIZE OF WINDOW SPECIFIED ON | | WINDOW SCHEDULE FOR BEDROOM #3. SEE PLAN |
|