2005-04-25 00:00:00 | ********** UNSAT ************* |
| |
| 1)NOTE: PLEASE SEE PANEL "A" SHOWS FEED |
| TO PANEL "B" AS 100A OCP ON #6 AWG. |
| PLEASE SEE 240.4,310.16 AND PLEASE |
| CORRELATE WITH RISER DIAGRAM. |
| PLEASE ALSO SEE THIS IS SHOWN AS 100A SP |
| BRKR ON ONE PHASE? (MISPRINT) |
| |
| 2)NOTE: PLEASE SEE PANEL "B" SHOWS SUB |
| PANEL "C" IN TWO DIFFERENT LOCATIONS? |
| PLEASE SEE THIS IS SHOWN ON SAME PHASE. |
| PLEASE ALSO CORRELATE AWG FOR 60A OCP. |
| SHOWS #6 AND #8? |
| PLEASE ALSO SEE SINGLE POLE 60A FOR |
| ADDITIONAL SUB PANEL. |
| PLEASE SEE 240.4,310.16, 310.15B6 |
| |
| 3)NOTE: PLEASE SEE NOTE ADDED TO CENTER |
| OF PLANS WHICH IS A PROVISO SET UP BY A |
| PLAN REVIEWER FOR A PREVIOUS PROJECT. |
| THIS COMMENT FROM OTHER ELECTRICAL PLAN |
| REVIEW SHOULD NOT BE LOCATED ON THESE |
| PLANS. |
| PLEASE REMOVE. |
| |
| 4)NOTE: PLEASE SEE SD'S ARE REQUIRED TO |
| BE WIRED "INLINE" ON THE SAME CIRCUIT, |
| HOWEVER PLANS INDICATE TWO SEPARATE |
| CIRCUITS FOR THE SD'S.THESE MAY NOT BE |
| ON THE SAME CIRCUIT. |
| NFPA-72 8-1.4.1.6.2 |
| |
| 5)NOTE: PLEASE SEE ONE OF THE ABOVE |
| CIRCUITS FOR SD'S (#38) IS THE SAME |
| CIRCUIT ON PANEL SCHEDULE FOR SUB PANEL |
| "B". |
| |
| 6)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS |
| ON PLANS. |
| 215.5 |
| |
| 7)NOTE: PLEASE SHOW LOADS ON EACH |
| ELECTRICAL PANEL. PANEL "B AND "C |
| MENTIONS TO SEE LOAD CALCS, HOWEVER |
| THESE PANELS NEED TO SHOW ACTUAL LOAD |
| FOR THOSE PANELS. |
| 220,215.5 |
| |
| 8 )NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| 9)NOTE: PLEASE SEE A JACUZZI/WHIRLPOOL |
| TUB IS SHOWN ON ON PANEL SCHEDULE, |
| HOWEVER THIS IS NOT SHOWN ON PLANS AT |
| WHAT APPEARS TO BE THE WP/JACUZZI TUB. |
| |
| 10)NOTE: PLEASE SEE MISSING GFI RECEPT |
| ON KITCHEN COUNTERSPACE. |
| 210.52C1,210.8A6 |
| |
| PLEASE BE SURE TO REMOVE ALL OLD VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. |
| PLEASE SEE ONE COPY/SET OF OLD SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE ONLY. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |