Plan Review Notes
Plan Review Notes For Permit 05040911
Permit Number 05040911
Review Stop E
Sequence Number 5
Notes
Date Text
2006-01-17 00:00:00REDLINED
  
 SEE BATH CIRCUIT #25 SHOWN ON PLANS,
 HOWEVER SHOWN AS COOKTOP ON PANEL
 SCHEDULE.
 OCP FOR AHU#2 SHOULD BE SIZED A MIN 125%
 PER 424.3B