2006-01-17 00:00:00 | REDLINED | | | | SEE BATH CIRCUIT #25 SHOWN ON PLANS, | | HOWEVER SHOWN AS COOKTOP ON PANEL | | SCHEDULE. | | OCP FOR AHU#2 SHOULD BE SIZED A MIN 125% | | PER 424.3B |
|