Date |
Text |
2005-08-31 00:00:00 | SUBMITTAL BUILDING REVIEW CHECKLIST; |
| 1- SEPARATE PERMIT FOR SHUTTERS HAS NOT |
| BEEN APPLIED FOR YET. |
| |
| 2- ENERGY CALCULATIONS WERE REVISED. NOW |
| CEILING FAN CREDIT WAS TAKEN. THEREFORE, |
| NEED TO REVISE ELECTRICAL PLAN SHOWING |
| SIZE OF CEILING FANS, INCLUDING FANS IN |
| THE GREAT ROOM AS REQUIRED BY TABLE 6-6 |
| OF CHAPTER 13 FBC 2001. |
| |
| 3- ROOF FRAMING PLAN NEEDS TO BE REVISE |
| AT ENTRY PORCH AREA TO MATCH FOUNDATION |
| PLAN AND FLOOR PLAN. NOTICE THAT |
| CONCRETE BEAM DOESN'T EXTEND ALL THE WAY |
| INSIDE TO THE FOYER AREA. CONCRETE BEAM |
| IS ONLY AT ENTRY PORCH AREA. REVISE AS |
| REQUIRED, INCLUDING TRUSS CONNECTORS AS |
| REQUIRED. SEC. 104.2.1.2 CITY AMENDMENTS |
| TO FBC 2001. |
| |
| 4- TRUSS ANCHOR SCHEDULE: REVISE NUMBER |
| OF NAILS SPECIFIED FOR CONNECTOR HUS26. |
| SEE 2005 CATALOGUE. |
| |
| 5- ONE HOUR FIRE RATED DOOR AT ATRIUM |
| PRODUCT APPROVAL SUBMITTED IS FOR |
| OUTSWING DOOR. PROVIDE INSWING DOOR AS |
| SHOWN ON PLANS OR REVISE PLANS AS REQ'D. |
| ***NOTE; DOOR NEED NOT TO BE FIRE RATED. |
| WALL IS CONSIDERED LIKE A FENCE NOT A |
| BUILDING WALL. THEREFORE, TABLE 600 FBC |
| 2001 DOESN'T APPLY. REVISE PLANS IF |
| SPECIFICATIONS CHANGE. |
| |
| 6- WINDOW MULLION SIZE SPECIFIED FOR |
| FIXED WINDOWS AT GREAT ROOM DOESN'T |
| RESIST THE CALCULATED DESIGN PRESSURES. |
| SEE PRODUCT APPROVAL AND REVISE SIZE OF |
| MULLION AS REQUIRED. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 7- ALL REVISED DRAWINGS WILL BE SUBJECT |
| TO THE REVISION FEES. SEE SUBMITTAL FORM |
| FOR APPLICABLE FEES. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT (561805-6712. |