Plan Review Notes For Permit 05040909 |
Permit Number |
05040909 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-06-10 00:00:00 | BUILDING REVIEW PROVISO: | | 1- SHUTTERS UNDER A SEPARATE PERMIT. | | 2- REVISE ENERGY CALCULATIONS. NEED THEM | | TO BE CALCULATED FOR WORST CASE SCENARIO | | 3- REVISE FRONT ELEVATION TO SHOW ENTRY | | DOORS AS SHOWN ON PRODUCT APPROVAL. | | 4- ROOF FRAMING PLAN: REVISE CONNECTOR | | SPECIFIED AT ENTRY PORCH. NEED MASONRY | | CONNECTOR. SEE DETAIL 5/D-1. | | 5- TRUSS ANCHOR SCHEDULE: REVISE TYPE OF | | NAIL USED FOR HUS26. SEE CATALOGUE. | | 6- PROVIDE PRODUCT APPROVAL FOR: A) ONE | | HR FIRE RATED ASSEMBLY AT EGRESS OPENING | | B) 12'-0" WIDE SLIDING GLASS DOORS. | | C) 8'-0" HIGH ENTRY DOORS. | | 7- PROVIDE CLEAR WINDOW AND DOOR | | SCHEDULES. NEED MATCHING SYMBOLS. | | 8- PROVIDE COPY OF EGRESS EASEMENT. |
|