2005-05-10 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- SOIL TEST REPORT RECOMMENDS 18" MIN.
 FOOTING WIDTH. FOUNDATION PLAN CALLS FOR
 16" WIDTH. REVISE AS REQUIRED.
  
 3- 45 DEGREE WINDOW ON BEDROOM #3 AT
 ZERO LOT LINE WALL IS NOT ALLOWED BY
 TABLE 600 FBC 2001. NO OPENINGS ALLOWED.
  
 4- PROVIDE NOTE ON DEN ROOM STATING THAT
 ROOM IS NOT ALLOWED TO BE USED FOR
 SLEEPING PURPOSES. OR, PROVIDE COMPLETE
 EGRESS REQUIREMENTS INCLUDING RECORDED
 EGRESS EASEMENT.
  
 5- PROVIDE DETAIL/SPECS FOR CEILING
 INSTALLATION AT ENTRY AND REAR PORCHES.
 SPECIFY FASTENERS TYPE AND SPACING . SEE
 SEC. 2504.2 FBC 2001.
  
 6- SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CONCRETE SLAB. SEE EXCEPTION IN SEC.
 1909.3 FBC 2001.
  
 7- SPECIFY FOOTINGS FOR ENTRY COLUMNS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 8- SHEET A-5.0:A) ROOF NAILING ZONE
 DIAPHRAGM IS MISSING ZONE 3. SEE FIGURE
 1606.2(C) FBC 2001.
  
 B) DETAIL 3 SPECIFIES HGUS 28-2 SIMPSON
 CONNECTOR IS A WOOD TO WOOD CONNECTOR.
 NEED TO SPECIFY CIFY WOOD TO MASONRY
 CONNECTOR. REVISE AS REQUIRED.
  
 C) DETAILS 1 AND 2: REVISE TYPE OF
 NAILS. SEE SIMPSON CATALOGUE.
  
 D) REVISE CONNECTOR SPECIFIED AT ENTRY
 PORCH. NEED MASONRY CONNECTOR. SEE
 DETAIL 5/D-1.
  
 9- REVISE/UPDATE TRUSS ANCHOR SCHEDULE.
 SEE LATEST CATALOGUE THAT WAS REVISED TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001.
 PROVIDE COMPLETE ENGINEERING CALCS FOR
 TYPE AND NUMBER OF NAILS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SECTION 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
  
 10- A)RIGHT SIDE ELEVATION DOESN'T MATCH
 PLANS. BATHROOM #2 HAS GLASS BLOCK NOT
 WINDOW.
  
 B) SHOW GLASS BLOCK ON LEFT ELEVATION TO
 MATCH PLAN.
  
 11- CLARIFY IF USING STORM SHUTTERS OR
 IMPACT GLAZING. THEN, PROVIDE COMPLETE
 INFORMATION FOR EITHER METHOD.
  
 12- PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL FOR:A) ONE HOUR FIRE RATED
 ASSEMBLY AT EMERGENCY EGRESS OPENING.
  
 B) SLIDING GLASS DOORS. DRAWINGS
 SUBMITTED DON'T MATCH DADE COUNTY NOA
 SUBMITTED.
  
 C) PROVIDE PRODUCT APPROVAL FOR 12'-0"
 WIDE SLIDING GLASS DOORS. SEE PLANS.
  
 D) LARGE FIXED WINDOWS AS SHOWN ON GREAT
 ROOM. PRODUCT APPROVAL SUBMITTED DOESN'T
 COVER THOSE SIZES.
  
 E) ENTRY DOORS. DRAWINGS SUBMITTED ARE
 FOR 6'-8" HIGH DOORS. SEE PLANS.
  
 F) TRUSS CONNECTORS SPECIFIED ON PLANS.
 AFTER CORRECTIONS TO SPECIFY PROPER
 ANCHORS ARE DONE ON PLANS.
  
 13- SHEET D-1:A) CONNECTORS CS-16 X
 AND HTS-20 SHOWN ON DETAILS 3, 4 AND 5
 ARE WOOD TO WOOD CONNECTORS. NEED TO
 SPECIFY MASONRY CONNECTORS. SEE
 CATALOGUE AND REVISE AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 B) REVISE TYPE AND NUMBER OF NAILS FOR
 HUS26 CONNECTOR. SEE CATALOGUE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.