2005-05-10 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- SOIL TEST REPORT RECOMMENDS 18" MIN. |
| FOOTING WIDTH. FOUNDATION PLAN CALLS FOR |
| 16" WIDTH. REVISE AS REQUIRED. |
| |
| 3- 45 DEGREE WINDOW ON BEDROOM #3 AT |
| ZERO LOT LINE WALL IS NOT ALLOWED BY |
| TABLE 600 FBC 2001. NO OPENINGS ALLOWED. |
| |
| 4- PROVIDE NOTE ON DEN ROOM STATING THAT |
| ROOM IS NOT ALLOWED TO BE USED FOR |
| SLEEPING PURPOSES. OR, PROVIDE COMPLETE |
| EGRESS REQUIREMENTS INCLUDING RECORDED |
| EGRESS EASEMENT. |
| |
| 5- PROVIDE DETAIL/SPECS FOR CEILING |
| INSTALLATION AT ENTRY AND REAR PORCHES. |
| SPECIFY FASTENERS TYPE AND SPACING . SEE |
| SEC. 2504.2 FBC 2001. |
| |
| 6- SPECIFY SUPPORTS AND SPACING FOR WWM |
| IN CONCRETE SLAB. SEE EXCEPTION IN SEC. |
| 1909.3 FBC 2001. |
| |
| 7- SPECIFY FOOTINGS FOR ENTRY COLUMNS. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| 8- SHEET A-5.0:A) ROOF NAILING ZONE |
| DIAPHRAGM IS MISSING ZONE 3. SEE FIGURE |
| 1606.2(C) FBC 2001. |
| |
| B) DETAIL 3 SPECIFIES HGUS 28-2 SIMPSON |
| CONNECTOR IS A WOOD TO WOOD CONNECTOR. |
| NEED TO SPECIFY CIFY WOOD TO MASONRY |
| CONNECTOR. REVISE AS REQUIRED. |
| |
| C) DETAILS 1 AND 2: REVISE TYPE OF |
| NAILS. SEE SIMPSON CATALOGUE. |
| |
| D) REVISE CONNECTOR SPECIFIED AT ENTRY |
| PORCH. NEED MASONRY CONNECTOR. SEE |
| DETAIL 5/D-1. |
| |
| 9- REVISE/UPDATE TRUSS ANCHOR SCHEDULE. |
| SEE LATEST CATALOGUE THAT WAS REVISED TO |
| COMPLY WITH SEC. 1609.4.3 FBC 2001. |
| PROVIDE COMPLETE ENGINEERING CALCS FOR |
| TYPE AND NUMBER OF NAILS THAT DIFFER |
| FROM THOSE TESTED AND PUBLISHED BY THE |
| MANUFACTURER. SECTION 104.2.1.2 OF CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 10- A)RIGHT SIDE ELEVATION DOESN'T MATCH |
| PLANS. BATHROOM #2 HAS GLASS BLOCK NOT |
| WINDOW. |
| |
| B) SHOW GLASS BLOCK ON LEFT ELEVATION TO |
| MATCH PLAN. |
| |
| 11- CLARIFY IF USING STORM SHUTTERS OR |
| IMPACT GLAZING. THEN, PROVIDE COMPLETE |
| INFORMATION FOR EITHER METHOD. |
| |
| 12- PROVIDE FLORIDA/LOCAL PRODUCT |
| APPROVAL FOR:A) ONE HOUR FIRE RATED |
| ASSEMBLY AT EMERGENCY EGRESS OPENING. |
| |
| B) SLIDING GLASS DOORS. DRAWINGS |
| SUBMITTED DON'T MATCH DADE COUNTY NOA |
| SUBMITTED. |
| |
| C) PROVIDE PRODUCT APPROVAL FOR 12'-0" |
| WIDE SLIDING GLASS DOORS. SEE PLANS. |
| |
| D) LARGE FIXED WINDOWS AS SHOWN ON GREAT |
| ROOM. PRODUCT APPROVAL SUBMITTED DOESN'T |
| COVER THOSE SIZES. |
| |
| E) ENTRY DOORS. DRAWINGS SUBMITTED ARE |
| FOR 6'-8" HIGH DOORS. SEE PLANS. |
| |
| F) TRUSS CONNECTORS SPECIFIED ON PLANS. |
| AFTER CORRECTIONS TO SPECIFY PROPER |
| ANCHORS ARE DONE ON PLANS. |
| |
| 13- SHEET D-1:A) CONNECTORS CS-16 X |
| AND HTS-20 SHOWN ON DETAILS 3, 4 AND 5 |
| ARE WOOD TO WOOD CONNECTORS. NEED TO |
| SPECIFY MASONRY CONNECTORS. SEE |
| CATALOGUE AND REVISE AS REQUIRED. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| B) REVISE TYPE AND NUMBER OF NAILS FOR |
| HUS26 CONNECTOR. SEE CATALOGUE. |
| |