Plan Review Notes
Plan Review Notes For Permit 05040907
Permit Number 05040907
Review Stop B
Sequence Number 2
Notes
Date Text
2005-06-08 00:00:00BUILDING REVIEW PROVISO:
 1- SHUTTERS UNDER SEPARATE PERMIT.
 2- USING SAME ENERGY CALCULATIONS FOR
 THIS MODEL, THEREFORE, NEED ENERGY
 CALCULATIONS FOR WORST CASE SCENARIO.
 REVISE ENERGY CALCS AS REQUIRED.
 3- REVISE DOOR SCHEDULE TO MATCH SIZES &
 TYPE OF DOORS SHOWN ON PLANS/ELEVATIONS.
 4- DETAIL 5/D-1: CONNECTOR HTS20 CAN'T
 SUPPORT BEAM. SPECIFY HANGER OR CLARIFY
 HOW IS BEAM SUPPORTED ON LEDGER.
 5- TRUSS ANCHOR SCHEDULE: UPDATE NAIL
 SIZE USED FOR HUS26 CONNECTOR.
 6- ROOF FRAMING PLAN: REVISE CONNECTOR
 SPECIFIED AT ENTRY PORCH TO MATCH
 DETAILS 5 & 6 OF DRAWING D-1.
 7- PROVIDE PRODUCT APPROVAL FOR 9'-0"
 WIDE SLIDING GLASS DOORS.
 8- SHEET A-5.0 SHEAR VALUES NOTE:
 A) PROVIDE HAND CALCULATIONS. SECTION
 104.2.1.2 CITY AMENDEMNTS TO FBC 2001.
 B) WHY USING TIMBER CONSTRUCTION MANUAL?
 SEE CHAPTER 23 FBC 2001.
 C) WHY USING TIMBER MANUAL TO CALCULATE
 TAPCON VALUES?