Plan Review Notes
Plan Review Notes For Permit 05040907
Permit Number 05040907
Review Stop B
Sequence Number 1
Notes
Date Text
2005-05-09 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- SOIL TEST REPORT RECOMMENDS 18" MIN.
 WIDTH FOR FOOTING. FOUNDATION PLAN CALLS
 FOR 16" WIDTH. REVISE AS REQUIRED.
  
 3- PROVIDE DETAIL/SPECS FOR CEILING
 INSTALLATION AT ENTRY AND REAR PORCHES.
 SPECIFY FASTENERS TYPE AND SPACING. SEE
 ASTM C-926 AND ASTM C-1063.
 SEC. 2504.2 FBC 2001.
 NOTE: ALSO, REVISE NAILING SCHEDULE NOTE
 FOR WIRE LATH ON SHEET D-1. HOW CAN YOU
 ACHIEVE 1 3/4" MIN. PENETRATION IF NAIL
 SIZE IS 1 1/4". SEE ASTM C-1063.
  
 4- SHEET A-1: A) REVISE FOOTING
 SPECIFIED FOR CONCRETE PAD AT COVERED
 PATIO. SEE PLANS FOR COMMENTS.
  
 B) SPECIFY FOOTING FOR ENTRY COLUMNS.
 SEC. 104.2.1.2 CITY AMENDMETNS TO FBC
  
 5- SHEET A-2.0:A) CLARIFY HOW CAN YOU
 HAVE 12'-0" CEILING AT LIVING ROOM
 FAMILY ROOM IF EXTERIOR ELEVATION SHOWS
 TOP OF BEAM AT 13'-0". IS THERE A DROP
 IN THE ROOF TRUSSES?. BLDG SECTION
 DOESN'T SHOW THAT. PROVIDE BLDG SECTION.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 B) SPECIFY GLASS BLOCK TO BE 1 HOUR FIRE
 RATED ASSEMBLY AT ZERO LOT LINE WALL.
 AS REQ'D BY TABLE 600 FBC 2001.
  
 6- FLOOR PLAN AND REAR ELEVATIONS DON'T
 MATCH. SEE MASTER BEDROOM WINDOWS AND
 DOORS SPECIFIED AND REVISE TO MATCH.
  
 7- SHEET A-5.0:A) NAILING SCHEDULE
 DIAPHRAGM IS MISSING ROOF ZONE #3. SEE
 FIGURE 1606.2(C) FBC 2001 AND REVISE.
  
 B) CLARIFY WHERE ARE THE SHEAR VALUES
 FOR NAILS AND TAPCONS TAKEN FROM? SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 C) TYPE OF BEAM SHOWN ON ROOF FRAMING
 PLAN AND EXTERIOR ELEVATIONS SHEET A-4.0
 DON'T MATCH. SEE DETAILS 6 AND 7 ON
 SHEET A-4.0 AND ROOF FRAMING PLAN.
 REVISE AS REQUIRED.
  
 D) TRUSS DESIGN CRITERIA CHART AND NOTE
 ON BOTTOM OF PAGE DON'T MATCH. SEE PLANS
 FOR COMMENTS.
  
 E) HGUS28-2 CONNECTOR SPECIFIED ON
 DETAIL #2 IS A WOOD TO WOOD CONNECTOR.
 NEED TO SPECIFY MASONRY CONNECTOR. SEE
 CATALOGUE AND REVISE AS REQUIRED.
  
 F) UPDATE/REVISE TRUSS ANCHOR SCHEDULE.
 SEE LATEST CATALOGUE THAT WAS REVISED TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001.
 PROVIDE COMPLETE ENGINEERING CALCS FOR
 CONNECTORS WITH FASTENER TYPE AND
 NUMBER THAT DIFFERFROM THOSE TESTED
 AND PUBLISHED. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 G) REVISE CONNECTORS SPECIFIED AT ENTRY
 PORCH BEAM. NEED MASONRY CONNECTOR. SEE
 DETAIL 6/D-1. AND REVISE TO MATCH. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 8- SHEET D-1:A) DETAIL #3 IS
 INCOMPLETE. MISSING HALF OF THE INFO.
  
 B) DETAILS 3,4,5 AND 6. REVISE
 CONNECTORSHTS-20, CS16X16" SPECIFIED.
 NEED MASONRY CONNECTORS. SEE CATALOGUE.
  
 9- CLARIFY IF USING IMPACT GLAZING IN
 DOORS/WINDOWS OR STORM SHUTTERS. PROVIDE
 COMPLETE INFO. FOR EITHER METHOD.
  
 10- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR: A) ENTRY DOORS. DRAWINGS
 SUBMITTED ARE FOR 6'-8" DOORS.
  
 B) ALL TRUSS ANCHORS SPECIFIED ON PLANS.
 AFTER CONNECTORS ARE REVISED.
  
 C) SLIDING GLASS DOORS WITH DRAWINGS
 THAT MATCH DADE COUNTY NOA. ALSO, NEED
 9'-0" WIDE SLIDING GLASS DOORS.
  
 D) FIXED LARGE WINDOWS AS SHOWN ON
 BREAKFAST AREA AND LIVING ROOM AREA.
 PRODUCT APPROVAL SUBMITTED DOESN'T COVER
 THESE WINDOW SIZES.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.