2005-05-09 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- SOIL TEST REPORT RECOMMENDS 18" MIN. |
| WIDTH FOR FOOTING. FOUNDATION PLAN CALLS |
| FOR 16" WIDTH. REVISE AS REQUIRED. |
| |
| 3- PROVIDE DETAIL/SPECS FOR CEILING |
| INSTALLATION AT ENTRY AND REAR PORCHES. |
| SPECIFY FASTENERS TYPE AND SPACING. SEE |
| ASTM C-926 AND ASTM C-1063. |
| SEC. 2504.2 FBC 2001. |
| NOTE: ALSO, REVISE NAILING SCHEDULE NOTE |
| FOR WIRE LATH ON SHEET D-1. HOW CAN YOU |
| ACHIEVE 1 3/4" MIN. PENETRATION IF NAIL |
| SIZE IS 1 1/4". SEE ASTM C-1063. |
| |
| 4- SHEET A-1: A) REVISE FOOTING |
| SPECIFIED FOR CONCRETE PAD AT COVERED |
| PATIO. SEE PLANS FOR COMMENTS. |
| |
| B) SPECIFY FOOTING FOR ENTRY COLUMNS. |
| SEC. 104.2.1.2 CITY AMENDMETNS TO FBC |
| |
| 5- SHEET A-2.0:A) CLARIFY HOW CAN YOU |
| HAVE 12'-0" CEILING AT LIVING ROOM |
| FAMILY ROOM IF EXTERIOR ELEVATION SHOWS |
| TOP OF BEAM AT 13'-0". IS THERE A DROP |
| IN THE ROOF TRUSSES?. BLDG SECTION |
| DOESN'T SHOW THAT. PROVIDE BLDG SECTION. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| B) SPECIFY GLASS BLOCK TO BE 1 HOUR FIRE |
| RATED ASSEMBLY AT ZERO LOT LINE WALL. |
| AS REQ'D BY TABLE 600 FBC 2001. |
| |
| 6- FLOOR PLAN AND REAR ELEVATIONS DON'T |
| MATCH. SEE MASTER BEDROOM WINDOWS AND |
| DOORS SPECIFIED AND REVISE TO MATCH. |
| |
| 7- SHEET A-5.0:A) NAILING SCHEDULE |
| DIAPHRAGM IS MISSING ROOF ZONE #3. SEE |
| FIGURE 1606.2(C) FBC 2001 AND REVISE. |
| |
| B) CLARIFY WHERE ARE THE SHEAR VALUES |
| FOR NAILS AND TAPCONS TAKEN FROM? SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| C) TYPE OF BEAM SHOWN ON ROOF FRAMING |
| PLAN AND EXTERIOR ELEVATIONS SHEET A-4.0 |
| DON'T MATCH. SEE DETAILS 6 AND 7 ON |
| SHEET A-4.0 AND ROOF FRAMING PLAN. |
| REVISE AS REQUIRED. |
| |
| D) TRUSS DESIGN CRITERIA CHART AND NOTE |
| ON BOTTOM OF PAGE DON'T MATCH. SEE PLANS |
| FOR COMMENTS. |
| |
| E) HGUS28-2 CONNECTOR SPECIFIED ON |
| DETAIL #2 IS A WOOD TO WOOD CONNECTOR. |
| NEED TO SPECIFY MASONRY CONNECTOR. SEE |
| CATALOGUE AND REVISE AS REQUIRED. |
| |
| F) UPDATE/REVISE TRUSS ANCHOR SCHEDULE. |
| SEE LATEST CATALOGUE THAT WAS REVISED TO |
| COMPLY WITH SEC. 1609.4.3 FBC 2001. |
| PROVIDE COMPLETE ENGINEERING CALCS FOR |
| CONNECTORS WITH FASTENER TYPE AND |
| NUMBER THAT DIFFERFROM THOSE TESTED |
| AND PUBLISHED. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| G) REVISE CONNECTORS SPECIFIED AT ENTRY |
| PORCH BEAM. NEED MASONRY CONNECTOR. SEE |
| DETAIL 6/D-1. AND REVISE TO MATCH. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 8- SHEET D-1:A) DETAIL #3 IS |
| INCOMPLETE. MISSING HALF OF THE INFO. |
| |
| B) DETAILS 3,4,5 AND 6. REVISE |
| CONNECTORSHTS-20, CS16X16" SPECIFIED. |
| NEED MASONRY CONNECTORS. SEE CATALOGUE. |
| |
| 9- CLARIFY IF USING IMPACT GLAZING IN |
| DOORS/WINDOWS OR STORM SHUTTERS. PROVIDE |
| COMPLETE INFO. FOR EITHER METHOD. |
| |
| 10- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: A) ENTRY DOORS. DRAWINGS |
| SUBMITTED ARE FOR 6'-8" DOORS. |
| |
| B) ALL TRUSS ANCHORS SPECIFIED ON PLANS. |
| AFTER CONNECTORS ARE REVISED. |
| |
| C) SLIDING GLASS DOORS WITH DRAWINGS |
| THAT MATCH DADE COUNTY NOA. ALSO, NEED |
| 9'-0" WIDE SLIDING GLASS DOORS. |
| |
| D) FIXED LARGE WINDOWS AS SHOWN ON |
| BREAKFAST AREA AND LIVING ROOM AREA. |
| PRODUCT APPROVAL SUBMITTED DOESN'T COVER |
| THESE WINDOW SIZES. |
| |
| |