Plan Review Notes For Permit 05040905 |
Permit Number |
05040905 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2006-01-09 00:00:00 | ********* UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE PANEL "A" IS MISSING | | LOAD FROM PANEL "B"AND "C". | | PLEASE ALSO SEE LOADS ON PANEL "B" AND | | "C". SOME ARE SHOWN WITH 83 KW, 96, KW | | ETC. | | PLEASE ADJUST LOADS AND CALCUALTIONS. | | 220, 215.5 | | | | 2)NOTE: PLEASE SEE MISSING RECEPT PER | | 210.52 | | | | 3)NOTE: PLEASE SEE A RECEPT IS STILL | | BEING SHOWN IN THE LOCATION OF THE NEW | | SLIDING GLASS DOORS.?? THIS HAS BEEN | | REMOVED ON SOME OTHER PLANS, HOWEVER NOT | | THIS PLAN. | | PLEASE SEE THIS WOULD BE A TRIPPING | | HAZARD AND NOT BE PERMITTED IN THIS | | EGRESS LOCATION. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|