Plan Review Notes For Permit 05040903 |
Permit Number |
05040903 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-06-29 00:00:00 | BUILDING REVIEW PROVISO: | | 1- SHUTTERS UNDER A SEPARATE PERMIT. | | 2- REVISE ENERGY CALCULATIONS TO BE | | WORST CASE SCENARIO. | | 3- REVISE DOOR AND WINDOW SCHEDULE TO | | MATCH FLOOR PLAN. INCLUDING SYMBOL USED. | | 4- DETAIL 5/D-1; CONNECTOR HTS20 CAN'T | | SUPPORT BEAM. REVISE AS REQUIRED. SEC. | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | 5- TRUSS ANCHOR SCHEDULE: UPDATE NAIL | | SIZE FOR HUS26 CONNECTOR. SEE CATALOGUE. | | 6- ROOF FRAMING PLAN: REVISE CONNECTOR | | SPECIFIED AT ENTRY PORCH TO MATCH | | DETAILS 5 & 6 OF DRAWINGS D-1. | | 7- PROVIDE PRODUCT APPROVAL FOR 9'-0" & | | 12'-0" WIDE SLIDING GLASS DOORS. | | 8- SHEET A-5.0 SHEAR VALUES NOTE: | | PROVIDE THE HAND CALCULATIONS. SECTION | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | B) SPECIFY EDITION OF THE MANUAL. | | C)WHY USING TIMBER MANUAL FOR TAPCONS. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | 9- REVISE REAR ELEVATION: 12'-0" WIDE | | SLIDING GLASS DOOR IS DRAWN INCORRECTLY. |
|