Plan Review Notes
Plan Review Notes For Permit 05040903
Permit Number 05040903
Review Stop B
Sequence Number 2
Notes
Date Text
2005-06-29 00:00:00BUILDING REVIEW PROVISO:
 1- SHUTTERS UNDER A SEPARATE PERMIT.
 2- REVISE ENERGY CALCULATIONS TO BE
 WORST CASE SCENARIO.
 3- REVISE DOOR AND WINDOW SCHEDULE TO
 MATCH FLOOR PLAN. INCLUDING SYMBOL USED.
 4- DETAIL 5/D-1; CONNECTOR HTS20 CAN'T
 SUPPORT BEAM. REVISE AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5- TRUSS ANCHOR SCHEDULE: UPDATE NAIL
 SIZE FOR HUS26 CONNECTOR. SEE CATALOGUE.
 6- ROOF FRAMING PLAN: REVISE CONNECTOR
 SPECIFIED AT ENTRY PORCH TO MATCH
 DETAILS 5 & 6 OF DRAWINGS D-1.
 7- PROVIDE PRODUCT APPROVAL FOR 9'-0" &
 12'-0" WIDE SLIDING GLASS DOORS.
 8- SHEET A-5.0 SHEAR VALUES NOTE:
 PROVIDE THE HAND CALCULATIONS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B) SPECIFY EDITION OF THE MANUAL.
 C)WHY USING TIMBER MANUAL FOR TAPCONS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 9- REVISE REAR ELEVATION: 12'-0" WIDE
 SLIDING GLASS DOOR IS DRAWN INCORRECTLY.