Plan Review Notes
Plan Review Notes For Permit 05040901
Permit Number 05040901
Review Stop E
Sequence Number 3
Notes
Date Text
2006-01-09 00:00:00********* UNSAT **********
  
  
 1)NOTE: PLEASE SEE PANEL "A" IS MISSING
 LOAD FROM PANEL "B"AND "C".
 PLEASE ALSO SEE LOADS ON PANEL "B" AND
 "C". SOME ARE SHOWN WITH 83 KW, 96, KW
 ETC.
 PLEASE ADJUST LOADS AND CALCUALTIONS.
 220, 215.5
  
 2)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52 DEN
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved