Plan Review Notes
Plan Review Notes For Permit 05040901
Permit Number 05040901
Review Stop B
Sequence Number 2
Notes
Date Text
2005-06-30 00:00:00BUILDING REVIEW PROVISO:
 1- SHUTTERS UNDER A SEPARATE PERMIT.
 2- NEED REVISED ENERGY CALCULATIONS FOR
 WORST CASE SCENARIO.
 3- REVISE DOOR/WINDOW SCHEDULE TO MATCH
 PLANS. INCLUDING SYMBOL USED.
 4- DETAIL 5/D1: CONNECTOR HTS20 CAN'T
 SUPPORT BEAM. REVISE AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5- TRUSS ANCHOR SCHEDULE: UPDATE NAIL
 SIZE USED FOR HUS26. SEE CATALOGUE.
 6- ROOF FRAMING PLAN: REVISE CONNECTOR
 SPECIFIED AT ENTRY PORCH TO MATCH
 DETAILS 5 & 6 OF DRAWING D-1.
 7- PROVIDE PRODUCT APPROVAL FOR:
 A) 9'-0" WIDE SLIDING GLASS DOORS.
 B) 8'-0" HIGH ENTRY DOORS.
 8- SHEET A-5 SHEAR VALUE NOTE:
 A) PROVIDE HAND CALCULATIONS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B) WHY USING TIMBER MANUAL TO CALCULATE
 TAPCON VALUES?.
 C) SPECIFY TIMBER MANUAL EDITION.