2005-11-15 00:00:00BUILDING SUBMITTAL CHECKLIST:
 1- NOW ENERGY CALCULATIONS WERE REVISED
 USING FBC 2004 FORM. THIS HOUSE WAS
 PERMITTED USING THE FBC 2001 FORMS.
 MIS-MATCHING CODES IS NOT ALLOWED.
 PROVIDE ENERGY CALCS USING THE FBC 2001
 FORMS AS REQUIRED.
  
 2- PROVIDE DETAIL 7/D1 AS KEYED ON
 REVISED ROOF FRAMING PLAN. THERE IS NOT
 DETAIL 7 ON SHEET D1.
  
 3- RESUBMIT FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR ONE HOUR FIRE RATED DOOR AT
 ATRIUM AS SPECIFIED ON PLANS:
 A) DRAWINGS SUBMITTED ARE FOR OUTSWING
 DOORS. NEED INSWING DOOR AS SHOWN ON
 PLANS AND DADE COUNTY NOA #02--0215.03
 SUBMITTED.
 B) DRAWINGS SUBMITTED ARE FOR 7'-0"
 HIGH DOORS. NEED 8'-0" HIGH DOOR AS
 SHOWN ON PLANS.
  
 4- APPLY FOR SHUTTERS UNDER A SEPARATE
 PERMIT AS AGREED ON PROVISO DATED 6-9-05
 TO AVOID DELAYS OR CONFLICTS GIVEN THE
 HIGH VOLUME OF APPLICATIONS AND THE
 SHORTAGE OF REVIEWING PERSONNEL.
  
 ***NOTE:
 STAMPED DRAWINGS AND PRODUCT APPROVAL
 ARE ALREADY APPROVED. CONTRACTOR TO KEEP
 THEM IN THE JOBSITE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.