Plan Review Notes For Permit 05040897 |
Permit Number |
05040897 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2005-11-15 00:00:00 | BUILDING SUBMITTAL CHECKLIST: | | 1- NOW ENERGY CALCULATIONS WERE REVISED | | USING FBC 2004 FORM. THIS HOUSE WAS | | PERMITTED USING THE FBC 2001 FORMS. | | MIS-MATCHING CODES IS NOT ALLOWED. | | PROVIDE ENERGY CALCS USING THE FBC 2001 | | FORMS AS REQUIRED. | | | | 2- PROVIDE DETAIL 7/D1 AS KEYED ON | | REVISED ROOF FRAMING PLAN. THERE IS NOT | | DETAIL 7 ON SHEET D1. | | | | 3- RESUBMIT FLORIDA OR LOCAL PRODUCT | | APPROVAL FOR ONE HOUR FIRE RATED DOOR AT | | ATRIUM AS SPECIFIED ON PLANS: | | A) DRAWINGS SUBMITTED ARE FOR OUTSWING | | DOORS. NEED INSWING DOOR AS SHOWN ON | | PLANS AND DADE COUNTY NOA #02--0215.03 | | SUBMITTED. | | B) DRAWINGS SUBMITTED ARE FOR 7'-0" | | HIGH DOORS. NEED 8'-0" HIGH DOOR AS | | SHOWN ON PLANS. | | | | 4- APPLY FOR SHUTTERS UNDER A SEPARATE | | PERMIT AS AGREED ON PROVISO DATED 6-9-05 | | TO AVOID DELAYS OR CONFLICTS GIVEN THE | | HIGH VOLUME OF APPLICATIONS AND THE | | SHORTAGE OF REVIEWING PERSONNEL. | | | | ***NOTE: | | STAMPED DRAWINGS AND PRODUCT APPROVAL | | ARE ALREADY APPROVED. CONTRACTOR TO KEEP | | THEM IN THE JOBSITE. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712. |
|