Plan Review Notes
Plan Review Notes For Permit 05040897
Permit Number 05040897
Review Stop B
Sequence Number 3
Notes
Date Text
2005-09-20 00:00:00BUILDING SUBMITTAL CHECKLIST:
 1- ENERGY CALCS WERE REVISED. NOW, THEY
 ARE TAKING THE CEILING FAN CREDIT.
 THEREFORE, NEED TO REVISE THE ELECTRICAL
 PLAN TO SHOW CEILING FAN SIZES IN ALL
 ROOMS AND THE CEILING FANS REQ'D FOR THE
 GREAT RM. SEE TABLE 6-6 CHAPTER 13 FBC.
 REVISION FEES WILL APPLY.
  
 2- REVISE ROOF FRAMING PLAN AT ENTRY
 PORCH. SHOW CORRECTLY WHEN THERE IS A
 CONCRETE BEAM OR WOOD BEAM. INCLUDING
 THE KNEEWALL AND SPECIFY CORRESPONDING
 CONNECTORS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC. REVISION FEES APPLY.
  
 3- REVISE NUMBER OF NAILS SPECIFIED
 FOR HUS26. SEE 2005 CATALOGUE.
  
 4- PROVIDE PRODUCT APPROVAL FOR ONE HR
 FIRE RATED ATRIUM DOOR THAT MATCHES
 PLANS.
  
 5- APPLY FOR SHUTTERS PERMIT AS AGREED
 ON PROVISO DATED 6-9-05.
  
 JULIO GOMEZ
 PLANS EXAMINER
 (561)805-6712.