2005-05-13 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOC.
  
 2- SOIL TEST REPORT RECOMMENDS 18" MIN.
 FOOTING WIDTH. FOUNDATION PLAN CALLS FOR
 16" WIDTH. REVISE AS REQUIRED.
  
 3- 45 DEGREE WINDOW ON BEDROOM #3 AT
 ZERO LOT LINE WALL IS NOT ALLOWED BY
 TABLE 600 FBC 2001.
  
 4- PROVIDE NOTE ON DEN ROOM STATING THAT
 ROOM IS NOT ALLOWED TO BE USED FOR
 SLEEPING PURPOSES. OR, PROVIDE COMPLETE
 EGRESS REQUIREMENTS INCLUDING RECORDED
 EGRESS EASEMENT.
  
 5- PROVIDE DETAIL/SPECS FOR CEILING
 INSTALLATION AT ENTRY AND REAR PORCHES.
 SPECIFY FASTENERS TYPE AND SPACING. SEE
 SECTION 2504.2 FBC 2001.
  
 6- SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CONCRETE SLAB. SEE EXCEPTION IN
 SECTION 1909.3 FBC 2001.
  
 7- SPECIFY FOOTINGS FOR ENTRY COLUMNS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 8- SHEET A-5.0:A) ROOF NAILING ZONE
 DIAPHRAGM IS MISSING ZONE 3. SEE FIGURE
 1606.2(C) FBC 2001.
  
 B) DETAIL 3 SPECIFIED HGUS 28-2 SIMPSON
 CONNECTOR IS A WOOD TO WOOD CONNECTOR.
 NEED TO SPECIFY WOOD TO MASONRY
 CONNECTOR. SEE CATALOGUE AND REVISE AS
 REQUIRED.
  
 C) DETAILS 1 AND 2: REVISE TYPE OF
 NAILS. SEE CATALOGUE.
  
 D) REVISE CONNECTOR SPECIFIED AT ENTRY
 PORCH. NEED MASONRY CONNECTOR. ALSO, SEE
 DETAIL 5/D-1 AND REVISE AS REQUIRED.
  
 9- REVISE/UPDATE TRUSS ANCHOR SCHEDULE.
 SEE LATEST CATALOGUE THAT WAS REVISED TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001.
 PROVIDE COMPLETE ENGINEERING CALCS FOR
 TYPE AND NUMBER OF NAILS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY
 MANUFACTURER. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 10- A) RIGHT SIDE ELEVATION DOESN'T
 MATCH PLANS. BATHROOM #2 HAS GLASS BLOCK
 NOT WINDOW. REVISE AS REQUIRED.
  
 B) SHOW GLASS BLOCK ON LEFT ELEVATION TO
 MATCH PLAN. REVISE AS REQUIRED.
  
 11- CLARIFY IF USING STORM SHUTTERS OR
 IMPACT GLAZING. THEN, PROVIDE COMPLETE
 INFORMATION FOR EITHER METHOD.
  
 12- PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL FOR:A) ONE HOUR FIRE RATED
 ASSEMBLY AT EMERGENCY EGRESS OPENING.
  
 B) SLIDING GLASS DOORS. DRAWINGS
 SUBMITTED DON'T MATCH DADE COUNTY NOA
 SUBMITTED.
  
 C) PROVIDE PRODUCT APPROVAL FOR 12'-0"
 WIDE SLIDING GLASS DOORS. SEE PLANS.
  
 D) LARGE FIXED WINDOWS AS SHOWN ON GREAT
 ROOM. PRODUCT APPROVAL SUBMITTED DOESN'T
 COVER THOSE SIZES.
  
 E) 8'-0" HIGH ENTRY DOORS. DRAWINGS
 SUBMITTED ARE FOR 6'-8" HIGH DOORS.
  
 F) ALL TRUSS CONNECTORS AS SPECIFIED ON
 PLANS AFTER THEY ARE REVISED.
  
 13- SHEET D-1:A) CONNECTORS CS-16X AND
 HTS-20 SHOWN ON DETAILS 3,4 AND 5 ARE
 WOOD TO WOOD CONNECTORS. NEED TO SPECIFY
 MASONRY CONNECTORS. SEE CATALOGUE AND
 REVISE AS REQUIRED. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 B) REVISE TYPE AND NUMBER OF NAILS FOR
 HUS26 CONNECTOR. SEE CATALOGUE.
  
 14- PLEASE DON'T STAPLE PRODUCT
 APPROVALS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL