Plan Review Notes For Permit 05040874 |
Permit Number |
05040874 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-12-05 00:00:00 | **** UNSAT **** | | | | | | 1)NOTE: PLEASE SEE MAIN PANEL INDICATES | | TWO POOL SUB PANELS? | | PLEASE LIST ACCORD AND PLEASE SHOW ALL | | PANELS ON PLANS AND LABEL. | | 215.5 | | | | 2)NOTE: PLEASE SUBMIT PANEL SCHEDULES | | FOR NEW PANEL "B" AND "C". | | SHOW LOADS. | | 215.5 | | | | 3)NOTE: PLEASE SEE ORIG PLANS WERE | | REDLINED FOR REQUIRED GFI PROTECTION TO | | BE INDICATED FOR WHIRLPOOL/JACUZZI TUB. | | 680.24 | | PLANS INDICATE A SPEACIAL PURPOSE | | CONNECTION, HOWEVER COULD NOT LOCATE ANY | | INDICATION ON PANEL SCHEDULE OR LOAD | | CALCS OF A JACUZZI TUB? | | PLEASE CORRELATE AND SHOW. | | 215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|