Plan Review Notes
Plan Review Notes For Permit 05040874
Permit Number 05040874
Review Stop E
Sequence Number 2
Notes
Date Text
2005-12-05 00:00:00**** UNSAT ****
  
  
 1)NOTE: PLEASE SEE MAIN PANEL INDICATES
 TWO POOL SUB PANELS?
 PLEASE LIST ACCORD AND PLEASE SHOW ALL
 PANELS ON PLANS AND LABEL.
 215.5
  
 2)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 FOR NEW PANEL "B" AND "C".
 SHOW LOADS.
 215.5
  
 3)NOTE: PLEASE SEE ORIG PLANS WERE
 REDLINED FOR REQUIRED GFI PROTECTION TO
 BE INDICATED FOR WHIRLPOOL/JACUZZI TUB.
 680.24
 PLANS INDICATE A SPEACIAL PURPOSE
 CONNECTION, HOWEVER COULD NOT LOCATE ANY
 INDICATION ON PANEL SCHEDULE OR LOAD
 CALCS OF A JACUZZI TUB?
 PLEASE CORRELATE AND SHOW.
 215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  