Plan Review Notes For Permit 05040760 |
Permit Number |
05040760 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-07-12 00:00:00 | | | PLEASE SEE 310.16 #10 CU MUST BE | | PROTECTED BY 30 AMP OCP MAX. THE | | SCHEMATIC SHOWS #10 SUB-PANEL FEEDERS | | AND #10 ON A 40 AMP BREAKER. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|