Plan Review Notes
Plan Review Notes For Permit 05040760
Permit Number 05040760
Review Stop E
Sequence Number 2
Notes
Date Text
2005-07-12 00:00:00 
 PLEASE SEE 310.16 #10 CU MUST BE
 PROTECTED BY 30 AMP OCP MAX. THE
 SCHEMATIC SHOWS #10 SUB-PANEL FEEDERS
 AND #10 ON A 40 AMP BREAKER.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW