Plan Review Notes For Permit 05040736 |
Permit Number |
05040736 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-06-29 00:00:00 | ****CORRECTIONS**** | | LOCAL PRODUCT APPROVAL | | SUBMITTED BY ADVANCED ROOFING | | 954-868-0063 | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2001 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2001 | | | | 1.) A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED, FS713.13. | | | | 2.)THE TESTING LAB IS NOT AN APPROVED | | TESTING LABORATORY, FAC9B72.100(3). | | | | 3.)THE THIRD PARTY QUALITY ASSURANCE | | ENTITY LISTED ON THE APPLICATION | | (UNDERWRITERS LABORATORY) HAS AN | | EXPIRATION DATE OF 6/30/2005.PRIOR TO | | RESUBMITTAL, PLEASE CONFIRM THAT THEIR | | APPROVAL WITH THE STATE IS CURRENT. | | WWW.FLORIDABUILDING.ORG | | | | 4.)THE PREVIOUS SUBMITTAL PROVIDED A | | DESIGN PRESSURE OF -263.8.THIS | | SUBMITTAL GIVES A DP OF -321 FOR ZONE 3. | | IT IS ACCEPTABLE TO INCREASE THE DP | | REQUIREMENT, BUT I AM BRINGING THIS | | DISCREPANCY TO YOUR ATTENTION. | | |
|