2005-04-25 00:00:00 | ******* UNSAT ********** |
| |
| 1)NOTE: PLEASE SEE NOE ELECTRICAL PLANS |
| FOR PROPOSED WORK WAS SUBMITTED, HOWEVER |
| AND ELECTRICAL PERMIT IS BEING |
| REQUESTED. |
| PLEASE SUBMIT ELECTRICAL DETAILS FOR |
| ELECTRICAL WORK BEING APPLIED FOR. |
| PLEASE SUBMIT SIGNED, SEALED PLANS BY A |
| FL REG PE. FS 471.003. |
| 215.5 |
| |
| 2)NOTE: PLEASE SEE FS 481.229 WHICH |
| REQUIRES PLANS TO BE SIGNED, DATED AND |
| SEALED FOR WORK OVER $25K FOR COMMERCIAL |
| BLDG. |
| PLEASE ALSO SEE PLANS WHICH CONTAIN A |
| TITLE BLOCK FOR AN ARCHITECTUAL FIRM ARE |
| REQUIRED TO BE SIGNED, DATED AND SEALED |
| BY SAID FIRM. |
| TITLE BLOCK SHALL CONTAIN ALL |
| INFORMATION AS SET-FORTH IN FAC |
| 61G1-16.004 , FS 481.219, 481.221 |
| PLEASE ALSO SEE ANY SHEETS BEING SIGNED |
| AND SEALED, MUST CONTAIN A TITLE BLOCK |
| AS STATED ABOVE. |
| |
| 3)NOTE: IF LIGHTNING PROTECTION SYSTEM |
| IS GOING TO BE INSTALLED AND UNDER THE |
| RESPONSIBLITY AND PERMIT OF ELECTRICAL |
| CONTRACTOR SIGNED ON APPLICATION, THEN |
| COMPLETE PLANS FOR INSTALLATIOON SHOWING |
| ALL DETAILS AND INSTALLATION OF SYSTEM |
| PER NFPA-780 SHALL BE SUBMITTED. |
| IF LIGHTING PROTECTION SYSTEM WILL BE A |
| SEPARATE PERMIT/PLANS, PLEASE REMOVE |
| FROM APPLICATION AND FROM PROPOSED WORK |
| ON DRAWINGS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |