Plan Review Notes
Plan Review Notes For Permit 05040598
Permit Number 05040598
Review Stop P
Sequence Number 1
Notes
Date Text
2005-05-05 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 1) SHT 2 PIPING SCHEMATIC DOES NOT
 REFLECT THE POOL LAYOUT ON SHT 1. THE
 POOL LAYOUT SHOWS SPA MAIN DRAINS, BUT
 THE PIPING SCHEMATIC DOES NOT. SECTION
 104.2.1.
 2) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. MANUF. SPECIFICATION SHEET DOES NOT
 SHOW POSITIVE MEANS OF RETAINING WATER
 IN THE HEAT PUMP. PLEAS INDICATE AN
 EXTERNAL HARTFORD LOOP TO SHOW
 COMPLIANCE WITH THIS CODE SECTION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]