Plan Review Notes
Plan Review Notes For Permit 05040550
Permit Number 05040550
Review Stop B
Sequence Number 1
Notes
Date Text
2005-04-11 00:00:00DENIED
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE ON THE APPLICATION. IF THE
 MEAN ROOF HEIGHT EXCEEDS THE LEAST
 HORIZONTAL DIMENSION OF THE STRUCTURE OR
 60 FEET WHICHEVER IS LESS, CALCULATIONS
 FOR THE UPLIFT PRESSURES FOR THE ROOFING
 FROM AN ENGINEER OR ARCHITECT IS
 REQUIRED. FBC 1606.2.1
  
 2) THE NOA THAT WAS SUBMITTED IS FOR
 WOOD DECK. DO THESE CONDOS HAVE WOOD OR
 CONCRETE DECKS? SPECIFY THE DECK
 MATERIAL ON THE APPLICATION.
  
 3) THE FLORIDA PRODUCT APPROVAL FL735
 HAS A DIFFERENT NOA # POSTED ON THE
 WEBSITE THAN THE ONE THAT WAS SUBMITTED.
 PLEASE SUBMIT THE CORRESPONDING NOA.
  
 4) INDICATED THE APPROVED ASSEMBLY FROM
 THE NOA THAT WILL BE INSTALLED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  