Plan Review Notes
Plan Review Notes For Permit 05040468
Permit Number 05040468
Review Stop G
Sequence Number 1
Notes
Date Text
2005-04-20 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 4) A GENERATOR PERMIT SHALL BE APPLIED
 FOR PRIOR TO GAS PERMIT BEING ISSUED. A
 SURVEY WILL BE SUBMITTED WITH THE
 GENERATOR PERMIT APPLICATION. THERE WILL
 BE A REVIEW BY STRUCTURAL, ELECTRICAL,
 ZONING, MECHANICAL, AND GAS PLAN REVIEW
 PERSONAL.
 5) SEARCH OF RECORDS INDICATE THAT THE
 POOL PLUMBING HAS NOT PASSED THE
 PERIMETER INSPECTION, NOR HAS IT HAD A
 FINAL PLUMBING INSPECTION. - A POOL
 PLUMBING PERMIT WILL BE REQUIRED TO DO
 THE PLUMBING TO THE POOL HEATER PRIOR TO
 GAS PERMIT BEING ISSUED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  