 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE TOTAL COMPUTED LOADS ON THE LOAD
 SUMMARY OF 178+92 EXCEED THE EXISTING
 SERVICE SIZE.
  
 2} 210.8(A)(6) KITCHENS -WHERE THE
 RECEPTACLES ARE INSTALLED TO SERVE THE
 COUNTERTOP SURFACES. REQUIRED GFI'S
  
 3} A RECEPTACLE MUST BE ADDED AT THE
 FRONT OF THE DWELLING PER 210.52(E).
  
 4} PLEASE NOTE THAT A RECEPTACLE AND
 LIGHT FIXTURE MUST BE ADDED IN THE ATTIC
 IF NONE EXISTS, FOR THE EQUIPMENT
 SERVICING PER 210.63 AND 210.70.
  
 5} THE ARCHITECT MUST SIGN AND SEAL BOTH
 SETS OF PLANS PER 481 FS.
  
 INCREASE THE APPLICATION VALUE TO
 REFLECT THE ADDITIONAL WIRING LABOR AND
 MATERIAL PER FBC 108.3.
  