2006-04-12 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE TOTAL COMPUTED LOADS ON THE LOAD | | SUMMARY OF 178+92 EXCEED THE EXISTING | | SERVICE SIZE. | | | | 2} 210.8(A)(6) KITCHENS -WHERE THE | | RECEPTACLES ARE INSTALLED TO SERVE THE | | COUNTERTOP SURFACES. REQUIRED GFI'S | | | | 3} A RECEPTACLE MUST BE ADDED AT THE | | FRONT OF THE DWELLING PER 210.52(E). | | | | 4} PLEASE NOTE THAT A RECEPTACLE AND | | LIGHT FIXTURE MUST BE ADDED IN THE ATTIC | | IF NONE EXISTS, FOR THE EQUIPMENT | | SERVICING PER 210.63 AND 210.70. | | | | 5} THE ARCHITECT MUST SIGN AND SEAL BOTH | | SETS OF PLANS PER 481 FS. | | | | INCREASE THE APPLICATION VALUE TO | | REFLECT THE ADDITIONAL WIRING LABOR AND | | MATERIAL PER FBC 108.3. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|