Plan Review Notes
Plan Review Notes For Permit 05040431
Permit Number 05040431
Review Stop E
Sequence Number 2
Notes
Date Text
2005-06-02 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} COMMENTS FROM PRIOR REVIEW, NOTE #3.
 3/0CU BEING FED WITH A 300 AMP BREAKER
 (OCP) IS IN VIOLATION OF 310.15(B)(6).
  
 2} THE QUESTION FROM COMMENT #1 STILL
 REMAAINS, IS THE SERVICE EQUIPMENT A
 METER/MAIN, IF SO USE CORRECT DIAGRAM
 FOR SAME, REMOVE THE 2" CONDUIT SHOWN ON
 RISER. IF NOT THE FEEDERS WOULD HAVE TO
 BE 250MCM TO COMPLY WITH 310.15,
 TERMINATING IN A 300 AMP OCP. IF THERE
 ARE QUESTIONS REGARDING THIS ISSUE, CALL
 DEWEY OR MYSELF PRIOR TO REDRAWING AND
 RESUBMITTING.
  
 3} NOTE #6. CLEARANCE FOR DISCONNECTS AT
 THE CONDENSERS, COMPLY WITH 110.26.
  
 4} NOTE #12, SUBMIT AIC(FAULT CURRENT)
 RATINGS FOR THE EQUIPMENT PER 110.10.
  
 5} IF THE OBJECT IN THE KITCHEN THAT
 RESEMBLES A TABLE, IS IN FACT AN ISLAND
 , THE RECEPTACLE MUST BE GFI PER
 210.8(A)(6).
  
 PLEASE LABEL THE ROOMS ON THE ELECTRICAL
 PLAN PER 104.2.1.3 FBC, CWPB
 AMMENDMENTS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  