2005-06-02 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} COMMENTS FROM PRIOR REVIEW, NOTE #3. | | 3/0CU BEING FED WITH A 300 AMP BREAKER | | (OCP) IS IN VIOLATION OF 310.15(B)(6). | | | | 2} THE QUESTION FROM COMMENT #1 STILL | | REMAAINS, IS THE SERVICE EQUIPMENT A | | METER/MAIN, IF SO USE CORRECT DIAGRAM | | FOR SAME, REMOVE THE 2" CONDUIT SHOWN ON | | RISER. IF NOT THE FEEDERS WOULD HAVE TO | | BE 250MCM TO COMPLY WITH 310.15, | | TERMINATING IN A 300 AMP OCP. IF THERE | | ARE QUESTIONS REGARDING THIS ISSUE, CALL | | DEWEY OR MYSELF PRIOR TO REDRAWING AND | | RESUBMITTING. | | | | 3} NOTE #6. CLEARANCE FOR DISCONNECTS AT | | THE CONDENSERS, COMPLY WITH 110.26. | | | | 4} NOTE #12, SUBMIT AIC(FAULT CURRENT) | | RATINGS FOR THE EQUIPMENT PER 110.10. | | | | 5} IF THE OBJECT IN THE KITCHEN THAT | | RESEMBLES A TABLE, IS IN FACT AN ISLAND | | , THE RECEPTACLE MUST BE GFI PER | | 210.8(A)(6). | | | | PLEASE LABEL THE ROOMS ON THE ELECTRICAL | | PLAN PER 104.2.1.3 FBC, CWPB | | AMMENDMENTS. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|