2005-04-13 00:00:00 | ********* UNSAT ********* |
| |
| 1)NOTE: PLEASE CLARIFY RISER, IT APPEARS |
| TO SHOW A METER/MAIN COMBO?? |
| PLEASE SEE RISER APPEARS TO SHOW A FEED |
| GOING OUT OF THE TOP OF EQUIPMENT TO A |
| SUB-PANEL? |
| 215.5 |
| PLEASE PROVIDE A PANEL SCHEDULE FOR |
| EQUIPMENT OUTSIDE IF INDEED A PANEL. |
| |
| 2)NOTE: PLEASE CLARIFY IF LOAD SHOWN FOR |
| POOL HEATER IS THE LOAD ALREADY FIGURED |
| AT 125% FOR CONTINUOUS LOADS. |
| 215.3,230.42 ETC. |
| |
| 3)NOTE: PLEASE SEE RISER SHOWS A 300A |
| MAIN WITH NO OCP SHOWN FOR SUB PANEL. |
| 300A MAIN ON 2/0'S?? |
| 240.4,310.15B6 |
| |
| 4)NOTE: PLEASE SEE 250.66 FOR MIN |
| GROUNDING ELECTRODE CONDUCTOR. #2 MIN |
| 310.15B6 |
| |
| 5)NOTE: PLEASE SEE 210.52D FOR MISSING |
| BATH RECEPTS WITHIN 3' OF SINK. |
| |
| 6)NOTE: PLEASE SEE MISSING A/C |
| DISCONNECTS FOR AC/ CU'S AND AHU'S. PER |
| 440.11 AND CLEARENCE PER 110.26 |
| |
| 7)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210.8A-6 |
| SEE ISLAND. |
| |
| 8)NOTE: PLEASE SEE 210.8A2 FOR GARAGES. |
| |
| 9)NOTE: PLEASE SEE PLANS ARE MISISNG ALL |
| SERVICE EQUIPMENT?? UNABLE TO REVIEW |
| LOCATIONS FOR CODE COMPLIANCE AT THIS |
| TIME.215. |
| |
| 10)NOTE:SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| :PLEASE SEE MISSING SD LEADING TO FLOOR |
| ABOVE: |
| |
| 11)NOTE: PLEASE SEE MISSING FOOTER STEEL |
| FOR GROUNDING ELECTRODE REQUIRED. 250.50 |
| |
| 12)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| PLEASE SEE MANY OF THE ABOVE ITEMS HAVE |
| BEEN REDLINED ON ONE SET OF PLANS. |
| |
| PLEASE REMOVE ALL OLD VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO TWOM |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONE SET/COPY OF OLD SHEETS SHOULD BE |
| SUBMITTED FOR REFERENCE ONLY. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |