Plan Review Notes
Plan Review Notes For Permit 05040431
Permit Number 05040431
Review Stop E
Sequence Number 1
Notes
Date Text
2005-04-13 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE CLARIFY RISER, IT APPEARS
 TO SHOW A METER/MAIN COMBO??
 PLEASE SEE RISER APPEARS TO SHOW A FEED
 GOING OUT OF THE TOP OF EQUIPMENT TO A
 SUB-PANEL?
 215.5
 PLEASE PROVIDE A PANEL SCHEDULE FOR
 EQUIPMENT OUTSIDE IF INDEED A PANEL.
  
 2)NOTE: PLEASE CLARIFY IF LOAD SHOWN FOR
 POOL HEATER IS THE LOAD ALREADY FIGURED
 AT 125% FOR CONTINUOUS LOADS.
 215.3,230.42 ETC.
  
 3)NOTE: PLEASE SEE RISER SHOWS A 300A
 MAIN WITH NO OCP SHOWN FOR SUB PANEL.
 300A MAIN ON 2/0'S??
 240.4,310.15B6
  
 4)NOTE: PLEASE SEE 250.66 FOR MIN
 GROUNDING ELECTRODE CONDUCTOR. #2 MIN
 310.15B6
  
 5)NOTE: PLEASE SEE 210.52D FOR MISSING
 BATH RECEPTS WITHIN 3' OF SINK.
  
 6)NOTE: PLEASE SEE MISSING A/C
 DISCONNECTS FOR AC/ CU'S AND AHU'S. PER
 440.11 AND CLEARENCE PER 110.26
  
 7)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 SEE ISLAND.
  
 8)NOTE: PLEASE SEE 210.8A2 FOR GARAGES.
  
 9)NOTE: PLEASE SEE PLANS ARE MISISNG ALL
 SERVICE EQUIPMENT?? UNABLE TO REVIEW
 LOCATIONS FOR CODE COMPLIANCE AT THIS
 TIME.215.
  
 10)NOTE:SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 :PLEASE SEE MISSING SD LEADING TO FLOOR
 ABOVE:
  
 11)NOTE: PLEASE SEE MISSING FOOTER STEEL
 FOR GROUNDING ELECTRODE REQUIRED. 250.50
  
 12)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 PLEASE SEE MANY OF THE ABOVE ITEMS HAVE
 BEEN REDLINED ON ONE SET OF PLANS.
  
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWOM
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET/COPY OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  