2005-05-06 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- SOIL TEST REPORT RECOMMENDS 18" MIN. |
| WIDTH FOR FOOTING. FOUNDATION PLAN CALLS |
| FOR 16". REVISE AS REQUIRED. |
| |
| 3- 45 DEGREE WINDOW ON BEDROOM #3 AT |
| ZERO LOT LINE WALL IS NOT ALLOWED BY |
| TABLE 600 FBC 2001. NO OPENINGS ALLOWED. |
| |
| 4- PROVIDE NOTE ON DEN ROOM STATING THAT |
| ROOM IS NOT ALLOWED TO BE USED FOR |
| SLEEPING PURPOSES. OTHERWISE, NEED TO |
| COMPLY WITH EGRESS REQUIREMENTS OF |
| SECTION 1005.4 FBC 2001. |
| |
| 5- NEED RECORDED EGRESS EASEMENT WHEN |
| USING THE ZERO LOT SIDE FOR EGRESS. SEE |
| ATTACHED REQUIREMENTS AND SAMPLE. |
| |
| 6- PROVIDE DETAIL/SPECS FOR CEILING |
| INSTALLATION AT ENTRY AND REAR PORCHES. |
| SPECIFY FASTENERS TYPE AND SPACING. SEE |
| ASTM C-926 AND ASTM C-1063. |
| SEC. 2504.2 FBC 2001. |
| |
| 7- SPECIFY SUPPORTS AND SPACING FOR WWM |
| IN CONCRETE SLAB. SEE EXCEPTION IN SEC. |
| 1909.3 FOR LOCATION OF WWM AND REVISE |
| NOTE ON FOUNDATION NOTE AS REQUIRED. |
| |
| 8- SPECIFY FOOTINGS FOR ENTRY COLUMNS. |
| SEC. 104.2.1.2 CITY AMENDEMNTS TO FBC. |
| |
| 9- SHEET A-5.0: A) ROOF NAILING ZONE |
| DIAPHRAGM IS MISSING ZONE #3. SEE FIGURE |
| 1606.2(C) FBC 2001.. |
| |
| B) DETAIL 3 SPECIFIES HGUS 28-2 SIMPSON |
| CONNECTOR. NEED TO SPECIFY WOOD TO |
| MASONRY CONNECTOR. REVISE AS REQUIRED. |
| |
| C) DETAIL 1 AND 2: REVISE TYPE OF NAILS. |
| SEE SIMPSON CATALOGUE. |
| |
| 10- REVISE/UPDATE TRUSS ANCHOR SCHEDULE |
| TO MATCH LATEST MANUFACTURER CATALOGUE |
| THAT WAS REVISED TO COMPLY WITH SECTION |
| 1609.4.3 FBC 2001. OTHERWISE, PROVIDE |
| COMPLETE ENGINEERING CALCULATIONS FOR |
| TYPE AND NUMBER OF FASTENERS THAT DIFFER |
| FROM THOSE TESTED AND PUBLISHED BY THE |
| MANUFACTURER. |
| |
| 11- RIGHT SIDE ELEVATION DOESN'T MATCH |
| PLANS. BATHROOM #2 NEED TO SHOW GLASS |
| BLOCK. |
| ALSO, SHOW GLASS BLOCK ON LEFT SIDE |
| ELEVATION. |
| |
| 12- CLARIFY IF USING DOORS AND WINDOWS |
| WITH IMPACT GLASS OR IF STORM SHUTTERS |
| ARE GOING TO BE USED. THEN, PROVIDE |
| COMPLETE INFORMATION FOR EITHER METHOD. |
| |
| 13- PROVIDE FLORIDA/LOCAL PRODUCT |
| APPROVAL FOR:A) 1 HOUR FIRE RATED |
| ASSEMBLY AT EMERGENCY EGRESS OPENING. |
| |
| B) SLIDING GLASS DOORS: DRAWINGS |
| SUBMITTED DON'T CORRESPOND TO DADE |
| COUNTY NOA. NEED DRAWING NO 4340. |
| |
| C) PROVIDE PRODUCT APPROVAL FOR 12'-0" |
| WIDE SLIDING GLASS DOORS. SEE PLANS. |
| |
| D) SIMPSON TRUSS CONNECTORS SPECIFIED ON |
| PLANS. SOME PRODUCT APPROVALS SUBMITED |
| ARE FOR CONNECTORS NOT SPECIFIED ON |
| PLANS. |
| |
| 14- SHEET D-1: A) CONNECTORS CS-16 X, |
| HTS-20 SHOWN ON DETAILS 3, 4 AND 5 ARE |
| WOOD TO WOOD CONNECTORS. NEED TO SPECIFY |
| CONNECTORS THAT ARE DESIGNED FOR MASONRY |
| APPLICATIONS. SEE SIMPSON CATALOGUE FOR |
| PROPER CONNECTOR SPECS AND PROPER TYPE |
| AND NUMBER OF FASTENERS. REVISE AS REQ'D |
| |
| |
| B) REVISE TYPE AND NUMBER OF NAILS |
| SPECIFIED ON DETAIL #4 FOR CONNECTOR |
| HUS26. SEE SIMPSON CATALOGUE. |
| |