Plan Review Notes
Plan Review Notes For Permit 05040426
Permit Number 05040426
Review Stop B
Sequence Number 1
Notes
Date Text
2005-05-06 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- SOIL TEST REPORT RECOMMENDS 18" MIN.
 WIDTH FOR FOOTING. FOUNDATION PLAN CALLS
 FOR 16". REVISE AS REQUIRED.
  
 3- 45 DEGREE WINDOW ON BEDROOM #3 AT
 ZERO LOT LINE WALL IS NOT ALLOWED BY
 TABLE 600 FBC 2001. NO OPENINGS ALLOWED.
  
 4- PROVIDE NOTE ON DEN ROOM STATING THAT
 ROOM IS NOT ALLOWED TO BE USED FOR
 SLEEPING PURPOSES. OTHERWISE, NEED TO
 COMPLY WITH EGRESS REQUIREMENTS OF
 SECTION 1005.4 FBC 2001.
  
 5- NEED RECORDED EGRESS EASEMENT WHEN
 USING THE ZERO LOT SIDE FOR EGRESS. SEE
 ATTACHED REQUIREMENTS AND SAMPLE.
  
 6- PROVIDE DETAIL/SPECS FOR CEILING
 INSTALLATION AT ENTRY AND REAR PORCHES.
 SPECIFY FASTENERS TYPE AND SPACING. SEE
 ASTM C-926 AND ASTM C-1063.
 SEC. 2504.2 FBC 2001.
  
 7- SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CONCRETE SLAB. SEE EXCEPTION IN SEC.
 1909.3 FOR LOCATION OF WWM AND REVISE
 NOTE ON FOUNDATION NOTE AS REQUIRED.
  
 8- SPECIFY FOOTINGS FOR ENTRY COLUMNS.
 SEC. 104.2.1.2 CITY AMENDEMNTS TO FBC.
  
 9- SHEET A-5.0: A) ROOF NAILING ZONE
 DIAPHRAGM IS MISSING ZONE #3. SEE FIGURE
 1606.2(C) FBC 2001..
  
 B) DETAIL 3 SPECIFIES HGUS 28-2 SIMPSON
 CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY CONNECTOR. REVISE AS REQUIRED.
  
 C) DETAIL 1 AND 2: REVISE TYPE OF NAILS.
 SEE SIMPSON CATALOGUE.
  
 10- REVISE/UPDATE TRUSS ANCHOR SCHEDULE
 TO MATCH LATEST MANUFACTURER CATALOGUE
 THAT WAS REVISED TO COMPLY WITH SECTION
 1609.4.3 FBC 2001. OTHERWISE, PROVIDE
 COMPLETE ENGINEERING CALCULATIONS FOR
 TYPE AND NUMBER OF FASTENERS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER.
  
 11- RIGHT SIDE ELEVATION DOESN'T MATCH
 PLANS. BATHROOM #2 NEED TO SHOW GLASS
 BLOCK.
 ALSO, SHOW GLASS BLOCK ON LEFT SIDE
 ELEVATION.
  
 12- CLARIFY IF USING DOORS AND WINDOWS
 WITH IMPACT GLASS OR IF STORM SHUTTERS
 ARE GOING TO BE USED. THEN, PROVIDE
 COMPLETE INFORMATION FOR EITHER METHOD.
  
 13- PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL FOR:A) 1 HOUR FIRE RATED
 ASSEMBLY AT EMERGENCY EGRESS OPENING.
  
 B) SLIDING GLASS DOORS: DRAWINGS
 SUBMITTED DON'T CORRESPOND TO DADE
 COUNTY NOA. NEED DRAWING NO 4340.
  
 C) PROVIDE PRODUCT APPROVAL FOR 12'-0"
 WIDE SLIDING GLASS DOORS. SEE PLANS.
  
 D) SIMPSON TRUSS CONNECTORS SPECIFIED ON
 PLANS. SOME PRODUCT APPROVALS SUBMITED
 ARE FOR CONNECTORS NOT SPECIFIED ON
 PLANS.
  
 14- SHEET D-1: A) CONNECTORS CS-16 X,
 HTS-20 SHOWN ON DETAILS 3, 4 AND 5 ARE
 WOOD TO WOOD CONNECTORS. NEED TO SPECIFY
 CONNECTORS THAT ARE DESIGNED FOR MASONRY
 APPLICATIONS. SEE SIMPSON CATALOGUE FOR
 PROPER CONNECTOR SPECS AND PROPER TYPE
 AND NUMBER OF FASTENERS. REVISE AS REQ'D
  
  
 B) REVISE TYPE AND NUMBER OF NAILS
 SPECIFIED ON DETAIL #4 FOR CONNECTOR
 HUS26. SEE SIMPSON CATALOGUE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  