Plan Review Notes
Plan Review Notes For Permit 05040423
Permit Number 05040423
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-04-18 00:00:001) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 2) DUCT SMOKE DETECTORS SHALL BE WIRED
 TO THE FIRE ALARM SYSTEM THAT WHEN
 ACTIVATED, WILL CAUSE A GENERAL FIRE
 ALARM, NOT SUPERVISORY SIGNAL.
  
 3) THE FIRE ALARM SYSTEM IS REQUIRED TO
 BE MONITORED BY A U.L. LISTED CENTRAL
 STATION SERVICE.
  
 4) A MINIMUM OF TWO SETS OF DRAWINGS ARE
 REQUIRED FOR REVIEW.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722