Plan Review Notes For Permit 05040385 |
Permit Number |
05040385 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-07-12 00:00:00 | DENIED | | | | THIRD REVIEW: | | | | OVERHEAD DOOR PRODUCT APPROVAL IS FOR A | | 16FT WIDE DOOR.DOORS ON PLANS ARE | | BETWEEN 9 - 10 FT WIDE. | | SUBMIT THE CORRECT PRODUCT APPROVAL FOR | | THE OVERHEAD DOORS. | | | | FLEMING DOOR STATE APPROVAL PAGE | | SUBMITTED IS NOT THE CORRECT PAGE. | | CLICK ON THE APPROPRIATE SERIES DOOR. | | SEE NOTE ON PAGE SUBMITTED. |
|