Plan Review Notes For Permit 05040385 |
Permit Number |
05040385 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-06-20 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE SUBMIT SPECIFICATIONS FOR THE | | TRANSFER SWITCH. SEE PREVIOUS REVIEW. | | | | 2} THE SERVICE INDICATES IT IS EXISTING. | | ON THE PREVIOUS PLAN IT WAS NEW. PLEASE | | CLARIFY | | | | 3} GIVE THE RATING OF THE SERVICE | | EQUIPMENT. AMPERAGE AND VOLTAGE. IF THIS | | IS A 300 AMP SERVICE, THE GEC MUST BE #2 | | PER 250.66. | | | | 4} SHOW THE LOCATION OF THE SERVICE | | EQUIPMENT ON THE PLAN. THE GENERATOR | | DISCONNECT IS NOT SHOWN. | | | | 5} THERE ARE TWO METERS SHOWN ON THE | | PLAN, ONLY ONE ON THE RISER. PLEASE | | CLARIFY.IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|