2005-06-20 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT SPECIFICATIONS FOR THE
 TRANSFER SWITCH. SEE PREVIOUS REVIEW.
  
 2} THE SERVICE INDICATES IT IS EXISTING.
 ON THE PREVIOUS PLAN IT WAS NEW. PLEASE
 CLARIFY
  
 3} GIVE THE RATING OF THE SERVICE
 EQUIPMENT. AMPERAGE AND VOLTAGE. IF THIS
 IS A 300 AMP SERVICE, THE GEC MUST BE #2
 PER 250.66.
  
 4} SHOW THE LOCATION OF THE SERVICE
 EQUIPMENT ON THE PLAN. THE GENERATOR
 DISCONNECT IS NOT SHOWN.
  
 5} THERE ARE TWO METERS SHOWN ON THE
 PLAN, ONLY ONE ON THE RISER. PLEASE
 CLARIFY.IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  