 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE SPECS FOR THE GENERATOR, ATS
 AND ALL RELATED EQUIPMENT.
  
 2} PROVIDE A SCHEMATIC INDICATING
 COMPLIANCE WITH ARTICLES 445,700.6 AND
 702 NEC.
  
 3} PLEASE INDICATE THE LOAD CALCULATION
 FOR THE CIRCUITS BEING FED FROM THE
 EMERGENCY PANEL. NOTE: CANNOT FEED 300
 AMP SERVICE FROM A 10K GENERATOR. SEE
 700.5.
  
 4} INDICATE THE PRIME MOVER FOR THE
 GENERATOR.
  
 5} PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED SERVICE SPECIFICATIONS PER
 215.15.
  
 6} THE PLANS MUST BE SIGNED AND SEALED
 PER 481 FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  