Plan Review Notes
Plan Review Notes For Permit 05040194
Permit Number 05040194
Review Stop B
Sequence Number 3
Notes
Date Text
2005-08-17 00:00:00BUILDING REVIEW THIRD CHECKLIST:
  
 1- ARCHITECT WAS ASKED TO REVISE THE
 ROOF LOADS CHART IN SHEET A2. REVISION
 WAS DONE BY WHITING OUT THE ATTIC LIVE
 LOAD AS REQUIRED BY TABLE 1604.1 FBC
 2001. NOW, CHART IS WRONG BECAUSE THE
 TOTAL LOAD WAS NOT REVISED ACCORDINGLY.
 TOTAL LOAD IS NOW 65PSF NOT 55PSF.
 REVISE AS REQUIRED.
 **NOTE: ARCHITECT TO SEE ATTACHED COPY
 OF FLORIDA STATUTE 553.80(2)(B)REGARDING
 MULTIPLE PLAN REVIEW DENIALS.
  
 2- ENERGY CALCULATIONS: A) AGAIN, IF THE
 ENERGY CALCULATIONS ARE PREPARED BY THE
 ARCHITECT THEY NEED TO BE SIGNED AND
 SEALED AS REQUIRED BY CHAPTER 481
 FLORIDA STATUTES.
  
 B) MISSING THE ADJACENT CEILING AREA.
  
 3- A) CLEARLY IDENTIFY SINGLE HUNG
 WINDOWS TO BE USED TO REVIEW FOR
 COMPLIANCE WITH THE CALCULATED DESIGN
 PRESSURES. CIRCLE IN THE DADE COUNTY NOA
 DRAWINGS SPECIFIC WINDOW (GLASS TYPE) TO
 BE USED.
 B) CLARIFY WHY HIGHLIGHTED WINDOW TYPE
 IN SHEET 3 OF THE FLORIDA PRODUCT
 APPROVAL CALLS FOR 435 LITEHOUSE MODEL,
 WHILE DADE COUNTY NOA CALLS FOR 435
 STORMBREAKER? IS THIS THE SAME MODEL.
 INFORMATION NEED TO MATCH INFORMATION
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL.
  
 4- NOTICE OF COMMENCEMENT EXPIRES AFTER
 90 DAYS IF WORK IS NOT STARTED. NEED
 RE-RECORDED NOC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.