2005-08-17 00:00:00 | BUILDING REVIEW THIRD CHECKLIST: |
| |
| 1- ARCHITECT WAS ASKED TO REVISE THE |
| ROOF LOADS CHART IN SHEET A2. REVISION |
| WAS DONE BY WHITING OUT THE ATTIC LIVE |
| LOAD AS REQUIRED BY TABLE 1604.1 FBC |
| 2001. NOW, CHART IS WRONG BECAUSE THE |
| TOTAL LOAD WAS NOT REVISED ACCORDINGLY. |
| TOTAL LOAD IS NOW 65PSF NOT 55PSF. |
| REVISE AS REQUIRED. |
| **NOTE: ARCHITECT TO SEE ATTACHED COPY |
| OF FLORIDA STATUTE 553.80(2)(B)REGARDING |
| MULTIPLE PLAN REVIEW DENIALS. |
| |
| 2- ENERGY CALCULATIONS: A) AGAIN, IF THE |
| ENERGY CALCULATIONS ARE PREPARED BY THE |
| ARCHITECT THEY NEED TO BE SIGNED AND |
| SEALED AS REQUIRED BY CHAPTER 481 |
| FLORIDA STATUTES. |
| |
| B) MISSING THE ADJACENT CEILING AREA. |
| |
| 3- A) CLEARLY IDENTIFY SINGLE HUNG |
| WINDOWS TO BE USED TO REVIEW FOR |
| COMPLIANCE WITH THE CALCULATED DESIGN |
| PRESSURES. CIRCLE IN THE DADE COUNTY NOA |
| DRAWINGS SPECIFIC WINDOW (GLASS TYPE) TO |
| BE USED. |
| B) CLARIFY WHY HIGHLIGHTED WINDOW TYPE |
| IN SHEET 3 OF THE FLORIDA PRODUCT |
| APPROVAL CALLS FOR 435 LITEHOUSE MODEL, |
| WHILE DADE COUNTY NOA CALLS FOR 435 |
| STORMBREAKER? IS THIS THE SAME MODEL. |
| INFORMATION NEED TO MATCH INFORMATION |
| SUBMITTED FOR FLORIDA PRODUCT APPROVAL. |
| |
| 4- NOTICE OF COMMENCEMENT EXPIRES AFTER |
| 90 DAYS IF WORK IS NOT STARTED. NEED |
| RE-RECORDED NOC. |
| |