Plan Review Notes
Plan Review Notes For Permit 05040194
Permit Number 05040194
Review Stop B
Sequence Number 2
Notes
Date Text
2005-07-22 00:00:00CHECKLIST:
 1- ROOF LOADS CHART IN SHEET A2 IS
 WRONG. IT'S NOT TAKING INTO
 CONSIDERATION THE ATTIC LIVE LOAD
 REQUIRED BY TABLE 1604.1 FBC 2001.
 (30PSF LIVE LOAD FOR STORAGE OR 10PSF
 LIVE LOAD WITHOUT STORAGE).
  
 2- STEPS AT ENTRY PORCH AND GARAGE DON'T
 COMPLY WITH SECTION 1007.3.1EXCEPTION
 #1. IT DOESN'T MEET THE REQUIRED RISER
 TREAD RATIO.
  
 3- REVISE ENERGY CALCULATIONS AGAIN:
 A) IF THEY ARE PREPARED BY THE
 ARCHITECT, THEY NEED TO BE SIGNED,
 SEALED AND DATED AS REQUIRED BY CHAPTER
 481 FLORIDA STATUTES.
 B) OVERHANG LENGTH AND HEIGHT ARE
 INCORRECT. SEE SEC. 601.2.A.3 CHAPTER 13
 OF FBC 2001.
 C) OWNER/AGENT TO SIGN AND DATE BOTTOM
 OF FORM.
 D) SLAB ON GRADE PERIMETER CALCULATION
 DOESN'T MATCH PLANS.
 E) NEED ADJACENT CEILING AREA.
  
 4- CLEARLY IDENTIFY SINGLE HUNG WINDOWS
 TO BE USED TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES SINCE
 PRODUCT APPROVAL SUBMITTED HAS SOME
 WINDOWS THAT DON'T MEET THOSE LOADS.
  
 5- SPECIFICATIONS FOR WIRE LATH IN THE
 FASTENER SCHEDULE DON'T MATCH
 SPECIFICATIONS SHOWN ON PORCH SECTION.
 REVISE AS REQUIRED.
  
 6- STAIR SECTION. CLEARLY INDICATE
 FIREBLOCKING IN STAIRWAY SECTION AS
 REQUIRED BY SEC. 2305.1.4 FBC 2001.
 (THERE WAS NOT LETTER ATTACHED WITH
 SUBMITTAL).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.