Plan Review Notes
Plan Review Notes For Permit 05040188
Permit Number 05040188
Review Stop B
Sequence Number 1
Notes
Date Text
2005-04-20 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PROPERTY APPRAISER'S DRAWING
 SHOWS THE SCREEN PORCH THAT IS BEING
 ENCLOSED TO BE 377 SQFT AND THE PLANS
 SPECIFY 261 SQFT. PLEASE CORRECT. THE
 PLANS WILL HAVE TO BE RESUBMITTED TO THE
 COUNTY FOR IMPACT FEES WITH THE CORRECT
 SQUARE FOOTAGE.
  
 3) SUBMIT THE STATE PRODUCT APPROVAL
 COVER SHEETS OR LOCAL PRODUCT APPROVAL
 FOR THE JELD-WEN DOORS.
  
 4) THE SH-701 (NON-IMPACT) WINDOWS ARE
 HI-LITED ON THE STATE PRODUCT APPROVAL
 COVER SHEET AND THE NOA THAT WAS
 SUBMITTED IS FOR THE SH-701 (IMPACT
 RESISTANT) WINDOWS. PLEASE CLARIFY.
  
 5) SUBMIT AN INSTALLATION SCHEDULE AND
 KEY PLAN FOR THE STORM PANELS. SPECIFY
 THE MOUNT TYPE AND FASTENERS THAT WILL
 BE USED.
  
 6) THE NOA THAT WAS SUBMITTED IS NOT THE
 ONE LISTED ON THE STATE WEBSITE FOR THIS
 STATE PRODUCT APPROVAL. NOA# 03-0421.13
 IS LISTED FOR THE 0.050 ALUMINUM PANELS.
  
 7) SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS AND LISTING FOR THE
 PREFAB FIREPLACE AND CHIMNEY.
  
 8) SHOW THE CHIMNEY ON THE ELEVATIONS
 AND SPECIFY THE HEIGHT ABOVE THE ROOF.
 SEE FBC 2804.2.4.
  
 9) PROVIDE A SECTION DETAIL OF THE WOOD
 FRAME CHIMNEY. SPECIFY ALL MECHANICAL
 CONNECTIONS, FRAMING MATERIAL, SPACING,
 EXTERIOR COVERING, ROOF FRAMING THAT
 WILL SUPPORT IT, ETC.
  
 10) SUBMIT ENERGY CALCULATION FORMS FOR
 THE ENCLOSED PORCH.
  
 11) THE DRAWING INDEX ON SHEET A1 OF THE
 PLANS LISTS THE ELECTRIC PLAN ON SHEET
 E1. THERE WAS NO SHEET E1 SUBMITTED.
  
 12) THE WALL SECTION ON D1 LISTS 2X6
 WALLS WITH R-11 INSULATION. CHAPTER 13
 SECTION 602.
  
 13) PROVIDE A CONNECTOR SCHEDULE AND
 SPECIFY THE CONNECTOR LOAD CAPACITIES.
 REVIEW ALL OF THE CONNECTORS SPECIFIED
 IN THE WALL SECTION AND OPENING FRAMING
 AND SPECIFY CURRENTLY AVAIALABLE
 CONNECTORS WITH STATE PRODUCT APPROVALS.
 THE CONNECTORS THAT ARE SPECIFIED MUST
 BE LISTED IN THE MANUFACTURER'S CATALOG
 FOR THAT APPLICATION. SIMPSON L50
 CONNECTORS ARE NOT FOR THE USE SHOWN ON
 THE PLANS.
  
 14) SPECIFY THE MECHANICAL CONNECTORS
 FOR ATTACHING THE ROOF FRAMING TO THE
 WALLS AND EXISTING HEADER.
  
 15) THE WALL SECTION AND THE WINDOW
 FRAMING DETAIL SPECIFY DIFFERENT ANCHORS
 AND LENGTHS. PLEASE CORRECT. SPECIFY AN
 ADEQUATE WASHER FOR THE ANCHOR BOLTS.
  
 16) SPECIFY THE CEILING HEIGHT IN THE
 ENCLOSED PORCH.
  
 17) SPECIFY THE CEILING FINISH.
  
 18) SPECIFY THE SOFFIT FINISH AND THE
 ATTIC VENTILATION. FBC 2309.7
  
 19) THE BUCK AND WINDOW MULL DETAILS ON
 SHEET D1 ARE FOR MASONRY CONSTRUCTION
 AND THE ADDITION IS WOOD FRAME.
  
 20) SPECIFY ON THE PLANS THAT ADEQUATE
 SUBSTRATE WILL BE INSTALLED FOR THE
 ATTACHMENT OF THE STORM PANELS.
  
 21) SEPARATE PERMITS ARE REQUIRED FOR
 ELECTRIC AND MECHANICAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  