Plan Review Notes For Permit 05040155 |
Permit Number |
05040155 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-05-23 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | 1) SHEET ATTACHED TO PLANS FOR HEAT PUMP | | TIE DOWN DETAIL NOT APPROVED. CODE CALLS | | FOR A NOMINAL 4" SUBSTANTIAL SLAB FOR | | MECHANICAL EQUIPMENT. DETAIL INDICATES | | THAT THE SLAB IS 3" PLEASE CORRECT THE | | DETAIL OR DELETE FROM PLANS. SECTION | | 1820.5. | | 2) POOL LAY OUT SHEET SHOWS 3 RETURNS TO | | THE POOL, BUT POOL SPECIFICATIONS | | INDICATE 8 RETURNS AS WELL AS THE RETURN | | DETAIL. PLEASE CORRELATE POOL LAYOUT | | WITH SPECIFICATIONS & RETURN DETAIL. | | 3) FBC-2001 424.2.14.1 SWIMMING POOL | | WATER HEATERS SHALL BEAR THE LABEL OF A | | RECOGNIZED TESTING AGENCY. MANUFACTURE | | SHEETS REQUIRED. (SUBMITTAL) | | 4) FBC-2001 424.2.14.2 WATER RETENTION, | | PROVIDE A POSITIVE MEANS OF RETAINING | | WATER IN THE HEATER WHEN PUMP IS SHUT | | OFF. (MANUF. CUT SHEETS - SUBMITTAL) | | 5) FBC-2001 424.2.14.4 CONNECTIONS, ALL | | WATER HEATING EQUIPMENT SHALL BE | | INSTALLED WITH FLANGES OR UNION | | CONNECTIONS ADJACENT TO THE WATER | | HEATER. (ADD TO NOTES). | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|