Plan Review Notes
Plan Review Notes For Permit 05040155
Permit Number 05040155
Review Stop P
Sequence Number 1
Notes
Date Text
2005-05-23 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) SHEET ATTACHED TO PLANS FOR HEAT PUMP
 TIE DOWN DETAIL NOT APPROVED. CODE CALLS
 FOR A NOMINAL 4" SUBSTANTIAL SLAB FOR
 MECHANICAL EQUIPMENT. DETAIL INDICATES
 THAT THE SLAB IS 3" PLEASE CORRECT THE
 DETAIL OR DELETE FROM PLANS. SECTION
 1820.5.
 2) POOL LAY OUT SHEET SHOWS 3 RETURNS TO
 THE POOL, BUT POOL SPECIFICATIONS
 INDICATE 8 RETURNS AS WELL AS THE RETURN
 DETAIL. PLEASE CORRELATE POOL LAYOUT
 WITH SPECIFICATIONS & RETURN DETAIL.
 3) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 4) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUF. CUT SHEETS - SUBMITTAL)
 5) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE WATER
 HEATER. (ADD TO NOTES).
  