Plan Review Notes For Permit 05040125 |
Permit Number |
05040125 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-04-07 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} HOW IS THE "EXISTING" 100 AMP | | SUB-PANEL, LOCATED AT THE GUEST | | HOUSE,FED AND GROUNDED. ITS NOT SHOWN ON | | THE RISER DIAGRAM. IS IT A SEPERATE | | SERVICE? | | | | 2} PLEASE SUBMIT LOAD CALCULATIONS PER | | ARTICLE 220 PART II, 220.30 OR 220.31. | | | | 3} IF AN EMERGENCY SYSTEM SUPPLIED BY A | | GENERATOR IS TO BE PART OF THIS PERMIT, | | PLEASE SUBMIT THE FOLLOWING. | | A) MFGR'S SPECS. | | B) INDICATE THE PRIME MOVER, AND HOW | | STORED. | | C) FEEDER CONDUCTOR SIZE. SEE 445.13. | | D) THE CONDUIT CONNECTING THE METER AND | | PANEL MUST BE REMOVED PER 700.6. | | E) INDICATE FRAME GROUND. | | | | 4} THE HALL IN THE HOUSE NEEDS A | | RECEPTACLE PER 210.52(H). | | | | 5} THE SMOKE DETECTOR IN THE KITCHEN | | MUST BE REMOVED OR BE PE TYPE. | | SEE8-4.1.2 NFPA-72. | | | | IF THERE ARE ANYQUESTIO0NS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|