 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} HOW IS THE "EXISTING" 100 AMP
 SUB-PANEL, LOCATED AT THE GUEST
 HOUSE,FED AND GROUNDED. ITS NOT SHOWN ON
 THE RISER DIAGRAM. IS IT A SEPERATE
 SERVICE?
  
 2} PLEASE SUBMIT LOAD CALCULATIONS PER
 ARTICLE 220 PART II, 220.30 OR 220.31.
  
 3} IF AN EMERGENCY SYSTEM SUPPLIED BY A
 GENERATOR IS TO BE PART OF THIS PERMIT,
 PLEASE SUBMIT THE FOLLOWING.
 A) MFGR'S SPECS.
 B) INDICATE THE PRIME MOVER, AND HOW
 STORED.
 C) FEEDER CONDUCTOR SIZE. SEE 445.13.
 D) THE CONDUIT CONNECTING THE METER AND
 PANEL MUST BE REMOVED PER 700.6.
 E) INDICATE FRAME GROUND.
  
 4} THE HALL IN THE HOUSE NEEDS A
 RECEPTACLE PER 210.52(H).
  
 5} THE SMOKE DETECTOR IN THE KITCHEN
 MUST BE REMOVED OR BE PE TYPE.
 SEE8-4.1.2 NFPA-72.
  