Plan Review Notes For Permit 05031898 |
Permit Number |
05031898 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-04-06 00:00:00 | PERMIT APPLICATIONWAS SUBMITTED | | WITHOUT PLANS.PLANS SUBMITTED WITH | | BUILDING PERMIT ARE NOT COMPLETE. | | PROVIDE THE FOLLOWING INFORMATION FOR | | REVIEW: | | - DISTANCE TO COMBUSTIBLES OR FIRE WRAP | | INFORMATION. | | - FPM WITHIN THE GREASE DUCT SYSTEM | | AS PER 2001 FBC/M 506.3.6 | | - PROVIDE MATERIAL OF GREASE DUCT IN | | ACCORDANCE WITH 2001 FBC/M 506.3.3. | | - GREASE DUCT TO HAVE A MINIMUM SLOPE | | OF 1/4" PER FT. | | - PROVIDE DETAIL FOR HANGING THE HOOD. | | | | SEE THE ATTACHED PROVISO, THIS WAS ON | | THE APPROVED MECHANICAL PLANS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|