2005-04-06 00:00:00PERMIT APPLICATIONWAS SUBMITTED
 WITHOUT PLANS.PLANS SUBMITTED WITH
 BUILDING PERMIT ARE NOT COMPLETE.
 PROVIDE THE FOLLOWING INFORMATION FOR
 REVIEW:
 - DISTANCE TO COMBUSTIBLES OR FIRE WRAP
 INFORMATION.
 - FPM WITHIN THE GREASE DUCT SYSTEM
 AS PER 2001 FBC/M 506.3.6
 - PROVIDE MATERIAL OF GREASE DUCT IN
 ACCORDANCE WITH 2001 FBC/M 506.3.3.
 - GREASE DUCT TO HAVE A MINIMUM SLOPE
 OF 1/4" PER FT.
 - PROVIDE DETAIL FOR HANGING THE HOOD.
  
 SEE THE ATTACHED PROVISO, THIS WAS ON
 THE APPROVED MECHANICAL PLANS.
  