Plan Review Notes For Permit 05031879 |
Permit Number |
05031879 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-04-16 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | 1. POOL LAYOUT SHEET (SHT 1), TABLE (SHT | | 2), AND APPROVED POOL DUAL MAIN DRAIN | | ATMOSPHERIC VENT ARRANGEMENT DETAIL (SHT | | 3) INDICATE A 1" VENT, BUT PLUMBING | | SCHEMATIC AND NOTE CONCERNING THE MAIN | | DRAINS INDICATE A 1-1/2" VENT. PLEASE | | CORRELATE PLANS. | | 2. SHT 2 PLUMBING SCHEMATIC AND SHT 3 | | VENT ARRANGEMENT DETAIL SHOW THE SUCTION | | LINE CONNECTING TO THE LINE AT THE | | CENTER OF THE MAIN DRAINS, BUT SHT ONE | | POOL LAYOUT SHOWS THE SUCTION LINE | | CONNECTING CLOSER TO ONE DRAIN THAN THE | | OTHER. SEE SECTION 424.2.6.6.4 INLETS | | SHALL BE PLUMBED SHUCH THAT WATER IS | | DRAWN THROUGH THEM SIMULATANEOUSLY. | | 3. FBC-2001 424.2.9 WATER SUPPLY, LOCAL | | ORD. #2853-95, BACKFLOW REQUIRED ON THE | | WATER SERVICE. (ADD TO NOTES). | | 4. INFORMATIONAL: HAND DRAWN CHANGES TO | | A SIGNED AND SEALED SET OF PLANS ARE NOT | | APPROVED. NEW SHEETS ARE REQUIRED FOR | | THESE CORRECTIONS, SIGNED & SEALED BY | | THE ENGINEER OF RECORD. SECTION | | 104.2.1.3. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|